Installation Manual

12
Lutronintegrationprotocol
MONITORING Command-specific fields
Monitoring Type:
Description Monitoring Type
Set(#)orGet(?)DiagnosticMonitoring 1
Set(#)orGet(?)EventMonitoring 2
Set(#)orGet(?)ButtonMonitoring
1
3
Set(#)orGet(?)LEDMonitoring
1,2
4
Set(#)orGet(?)ZoneMonitoring
1
5
Set(#)orGet(?)Occupancy
1
6
Set(#)orGet(?)PhotoSensorMonitoring 7
Set(#)orGet(?)Scene#
1
8
Set(#)orGet(?)SystemVariable 10
Set(#)orGet(?)ReplyState(ifdisabled,allmessagesFROMtheintegrationaccesspoint
willcease)
1,3
11
Set(#)orGet(?)PromptState(ifdisabled,thepromptwillnotbeprintedtotheterminal)
1,3
12
Set(#)orGet(?)OccupancyGroupMonitoring 13
Set(#)orGet(?)DeviceLockStateMonitoring 14
Set(#)orGet(?)SequenceMonitoring
2
16
Set(#)orGet(?)HVACMonitoring
1,2,4
17
Set(#)orGet(?)ModeMonitoring
1,2,4
18
Set(#)orGet(?)ShadeGroupMonitoring
1,5
23
Set(#)orGet(?)PartitionWall
5,6
24
Set(#)orGet(?)TemperatureSensorMonitoring
1,7
27
Set(#)orGet(?)StateofAllMonitoring(exceptReplyandPrompt) 255
NOTES
1  Thefollowingmonitoringtypesareenabledbydefault,foruser-leveltelnetlogin:3-Button,4-LED,5-Zone,6-Occupancy,
8-Scene,11-Reply,12-Prompt,17-HVAC,18-Mode,23-Shade
2  NotsupportedinQSStandalone
3  Thefollowingmonitoringtypesareenabledbydefault,foradmin-leveltelnetlogin:11-Reply,12-Prompt
4  NotcompatiblewithQuantum
5  NotsupportedinRadioRA2andHomeWorksQS
6  NotsupportedviaQSE-CI-NWK-EinQuantum
7  SupportedbyPalladiomThermostatonly
Action Numbers:
Action Action Number
Enable 1
Disable 2
MONITORING Command Formats
Use “MONITORING Command-specific fields” tables
to complete these command fields.
Operation
Command
#MONITORING,MonitoringType,ActionNumber
Integrator’s Reference (continued)
MONITORING: Command Summary
Monitoringallowstheusertocongurewhattypesofmessagesthesystemwillreport
Note to Integrator:The default values of these are set in the programming database and restored
whenever the integration port is logged in. The user can temporarily change those settings to hide