Installation Manual
13
Lutronintegrationprotocol
ERROR Command Formats
Refer to “ERROR Command-specific fields” table
Operation
Command
~ERROR,ErrorNumber
ERROR Command-specific fields
Error Numbers:
Description Error Number
Report(~)Parametercountmismatch 1
Report(~)Objectdoesnotexist 2
Report(~)Invalidactionnumber 3
Report(~)Parameterdataoutofrange 4
Report(~)Parameterdatamalformed 5
Report(~)UnsupportedCommand 6
Example ERROR Messages
Operation Command String
Parameter count mismatch: Toomanyortoofewparametersforthespeciedaction
Toomanyparameterswhenactivatingscene #AREA,2,6,1,1,1,1,1<CR><LF>
Parametercountmismatch ~ERROR,1<CR><LF>
Object does not exist: TheIntegrationIDorserialnumberentereddoesnotmaptoaknownpartofthesystem
SendcommandtoanIDthatisnotvalid #OUTPUT,1234,1,100.00<CR><LF>
Objectdoesnotexist ~ERROR,2<CR><LF>
Invalid Action: Theactiondoesnotexistforthiscommand
Sendinvalidaction(4321)toArea2 #AREA,2,4321<CR><LF>
Invalidactionnumber ~ERROR,3<CR><LF>
Parameter data out of range: Theparameterdataisoutofrangeforthisaction
SendOutput11to120% #OUTPUT,11,1,120.00<CR><LF>
Parameterdataoutofrange ~ERROR,4<CR><LF>
Parameter data malformed:Theparameterdatagivenwasnotformattedproperly
SetTimeto12:23:24:25 #SYSTEM,1,12:23:24:25<CR><LF>
Invalidactionnumber ~ERROR,5<CR><LF>
Integrator’s Reference (continued)
ERROR: Command Summary
IntegrationAccessPointswillrespondwithanerrorifaninvalidcommandisreceived Seethe
tablebelowforexplanationsofdifferenterrors