Installation Manual

25
Lutron integration protocol
PROGRAMING Command Formats
PROGRAMMING Command-specific fields
Action NumbersandParameters:
Description Action Number Parameters
Get(?)displayprogrammingofaspecicphantom
button
1
None None
Get(?)displayStop-If-Movingcongurationofa
specicphantombutton
2
4 None
Example PROGRAMMING Commands
Thefollowingexamplesshowhowtoverifytheprogrammingofthephantombuttonsofa
QSE-CI-NWK-EwithanIntegrationIDof“1 ”
Operation Command String
Displayprogrammingofphantombutton1 ?PROGRAMMING,1,1<CR><LF>
Displayprogrammingofallphantombuttons ?PROGRAMMING,1<CR><LF>
DisplayStop-If-Movingcongurationofphantombutton5 ?PROGRAMMING,1,5,4<CR><LF>
DisplayStop-If-Movingcongurationofallphantombuttons ?PROGRAMMING,1,0,4<CR><LF>
NOTES
1  Todisplayprogrammingofallphantombuttons,leavethebuttonnumbereldblank
2  TodisplayStop-If-Movingcongurationofallphantombuttons,usebuttonnumber0
Operation
Command
?PROGRAMMING,1,ButtonNumber,ActionNumber
Integration ID or Serial # of
the QSE-CI-NWK being used
Use “PROGRAMMING Command-specific fields” tables
to complete these command fields.
Phantom Button Number
(can be 1100)
QS Standalone (continued)
System Commands (continued)
PROGRAMMINGCommands(continued)
Continuedonnextpage…