Installation Manual
26
Lutron integration protocol
QS Standalone (continued)
System Commands (continued)
DEVICECommands
DEVICE Command Formats
DEVICE Command-specific fields
Action Numbers and Parameters:
Description Action Number Parameters
Set(#)activatethephantombuttonpreset 3 None
Set(#)acustomleveloftheshades,lightingzones
programmedtothephantombutton
1
14 Level:Theleveltheshadeswillgoto
1
Set(#)StartRaisingShades
2
18 None
Set(#)StartLoweringShades
2
19 None
Set(#)StopRaisingorLoweringShades 20 None
Set(#)acustomliftandtiltlevelofvenetianblindspro-
grammedtothephantombutton
1
23 Liftlevel%
Tiltlevel%
Set(#)acustomliftlevelonlyofvenetianblindspro-
grammedtothephantombutton
1
24 Liftlevel%
Set(#)acustomtiltlevelonlyofvenetianblindspro-
grammedtothephantombutton
1
25 Tiltlevel%
NOTES
1 Specifyingacustomlevelabovewillnotaffectthepresetlevelprogrammedforthephantombutton
2 ForVenetianblinds,theRaise&LowerActionswillaffecteithertheliftorthetiltbasedonhowthephantombuttonwas
programmed If#PROGRAMMINGAction5isused(affectingbothliftandtiltlevels),thentheRaise&LowerActionswill
affectthetilt
Example DEVICE Commands
Thefollowingexamplesshowhowwecanactivatephantombuttonsonalinkwitha
QSE-CI-NWK-EwhoseIntegrationIDis“1 ”
Operation Command String
ActivatePresetonphantombutton1 #DEVICE,1,1,3<CR><LF>
Setthelevelofallshadesprogrammedtophantombutton2to50% #DEVICE,1,2,14,50<CR><LF>
Setallvenetianblindsprogrammedtophantombutton3toaliftlevelof
50%andtiltlevelof25%
#DEVICE,1,3,23,50,25<CR><LF>
Setallvenetianblindsprogrammedtophantombutton4toaliftlevelof50% #DEVICE,1,4,24,50<CR><LF>
Setallvenetianblindsprogrammedtophantombutton5toatiltlevelof25% #DEVICE,1,5,25,25<CR><LF>
Raisetheshadesandvenetianblindsprogrammedtophantombutton6 #DEVICE,1,6,18<CR><LF>
Lowershadesandvenetianblindsprogrammedtophantombutton7 #DEVICE,1,7,19<CR><LF>
Stopshadesandvenetianblindsprogrammedtophantombutton8 #DEVICE,1,8,20<CR><LF>
Operation
Command
Integration ID or Serial # of
the QSE-CI-NWK being used
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Phantom Button Number
(can be 1–100)
#DEVICE,1,ButtonNumber,ActionNumber,Parameters