Installation Manual

38
Lutron integration protocol
INTEGRATION ID Command Formats
INTEGRATION ID Command-specific fields
Action NumbersandParameters:
Description Action Number Parameters
Get(?)IntegrationIDforaSerial
Number
1 SerialNumber:8characterHEXserialnumberofthedevice;
IntegrationID:TheintegrationIDtobeassigned
Get(?)InfofromID 3 IntegrationID=TheIntegrationIDthatinformationisdesiredfor
Note:Ifthiseldisleftblank,allintegrationIDswillbeprinted
Example INTEGRATION ID Commands
Operation Command String
Execute: ?INTEGRATIONID,ActionNumber,Parameters
GettheIntegrationIDforaserialnumber ?INTEGRATIONID,1,5678EFEF<CR><LF>
Response: ~INTEGRATIONID,ActionNumber,Parameters
GettheIntegrationIDforaserialnumber ~INTEGRATIONID,1,5678EFEF,1<CR><LF>
Execute: ?INTEGRATIONID,ActionNumber,Parameters
GetinformationaboutanIntegrationIDcommand ?INTEGRATIONID,3,1<CR><LF>
Response: ~INTEGRATIONID,ActionNumber,Parameters
GetinformationaboutanIntegrationIDcommand ~INTEGRATIONID,3,1,DEVICE,5678EFEF<CR><LF>
Quantum (continued)
System Commands (continued)
INTEGRATIONIDCommands
Use “INTEGRATIONID Command-specific fields” tables
to complete these command fields.
Operation
Command
?INTEGRATIONID,ActionNumber,Parameters