Installation Manual

40
Lutron integration protocol
AREA Command Formats
AREA Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)AreaLevel 1 Level
1
=0–100or0 00 –100 00
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising
4
2 None
Set(#)StartLowering
4
3 None
Set(#)StopRaisingorLowering 4 None
Set(#)orGet(?)CurrentScene 6 SceneNumber
5
= 0 3 2
6
Set(#)orGet(?)DaylightingMode 7 1=Active
2=Inactive
Get(?)OccupancyState 8 1=Unknown
2=Inactive
3=Occupied
4=Unoccupied
Set(#)orGet(?)OccupancyMode 9 1=OccupancyandVacancy
7
2=Vacancy
7
3=NotApplicable
8
4=Inactive
Set(#)orGet(?)OccupiedLevelorScene 12 Level
=0–100;200–232forSceneNumber=032
Set(#)orGet(?)UnoccupiedLevelorScene 13 Level
=0–100;200–232forSceneNumber=032
Set(#)orGet(?)HyperionShadowSensor
OverrideState
9
26 0=Disable
1=Enable
2=Mixed(GetOnly)
Set(#)orGet(?)HyperionBrightnessSensor
OverrideState
9
27 0=Disable
1=Enable
2=Mixed(GetOnly)
NOTES
1  TheLevelisacceptedasapercentage
2  TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-second
delay Theminimumfadeanddelaytimeis0seconds Themaximumfadeanddelaytimeis4hours
3  Fractionalseconds“SS ss”willberoundeddowntothenearestquarter-second Forexample,ifafadetimeisspecied
as1 45secondsavalueof1 25secondswillbeused
4  WhenaRaise/Lowercommandisissued,thearea’slevelwillcontinuetogotowardshighend/lowenduntilaStop
commandisreceived
5  Scene0istheOffScene
6  Scenes17–32availableonlyonSlider
7  IfAfterHoursisusedinanarea,settingthearea’sOccupancyModeto“OccupancyandVacancy”or“Vacancy”will
activateAfterHours
8  Theareawillreport“NotApplicable”asitsOccupancyModeiftheareadoesnothaveoccupancysensorsandifAfter
Hoursisnotused
9  Quantum2 7andhigher
Quantum (continued)
System Commands (continued)
AREACommands
Use “AREA Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#AREA
1,2
,2,ActionNumber,Parameters
NOTES
1  AREAcanbeusedtocontrolonlythoseareasofaQuantumsystemthathavebeenassignedtoaparticularintegration
accesspoint PleaserefertotheQ-Designsoftware(IntegrationTab)orQuantumIntegrationReportfordetailsofwhat
areasareavailableforcontrolandmonitoring
2  AREAcommandscannotbesenttoareasthatcontainotherareas,suchasaoororanentirebuilding
Continuedonnextpage…