Installation Manual
43
Lutron integration protocol
OUTPUT Command Format
OUTPUT Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)OutputLevel 1 Level
1
=0–100or0 00 –100 00
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising
4
2 None
Set(#)StartLowering
4
3 None
Set(#)StopRaisingorLowering
4
4 None
Set(#)PulseTime 6 Pulse
5
timein:SS ss
3
,SS,MM:SS,orHH:MM:SS,or
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)DMXColororLevelSettings
6
17 Color/levelindex:0–255
0 00–100 00
5
Set(#)MotorJogRaise
6,7
18 None
Set(#)MotorJogLower
6,7
19 None
Set(#)Motor4-StageJogRaise
6,7
20 None
Set(#)Motor4-StageJogLower
6,7
21 None
NOTES
1 TheLevelistakenasapercentage
2 TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-second
delay Theminimumfadeanddelaytimeis0seconds Themaximumfadeanddelaytimeis4hours Forshadeoutputs,
theFadeparameterhasnoeffect(sinceshadeshavexedspeeds)butitisrequiredwhenspecifyinganoptionaldelay
3 Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifafadetimeisspecied
as1 45secondsavalueof1 25secondswillbeused
4 WhenaRaise/Lowercommandisissued,theoutput’slevelwillcontinuetogotowardshighend/lowenduntilaStop
commandisreceived
5 Thedefaulttimeisonesecond
6 NotsupportedinRadioRA2
7 Quantum2 5andup
Quantum (continued)
System Commands (continued)
OUTPUTCommands
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT
1
,2,ActionNumber,Parameters
NOTE
1 OUTPUTcommandscanbeusedtocontrolsystemlightingzones,contactclosedoutputsandACMotorLoads
Continuedonnextpage…