Installation Manual

51
Lutron integration protocol
Example OUTPUT Messages
Operation Command String
Execute: #OUTPUT,IntegrationID,ActionNumber,Parameters
Setoutputlevelto70%(Fade=4sec,Delay=2sec) #OUTPUT,2,1,70,4,2<CR><LF>
RaiseOutput #OUTPUT,2,2<CR><LF>
Query: ?OUTPUT,IntegrationID
Whatisthecurrentoutputlevel? ?OUTPUT,2<CR><LF>
Response
1
: ~OUTPUT,IntegrationID,ActionNumber,Parameters
Outputlevelissetto48% ~OUTPUT,2,1,48<CR><LF>
NOTE
1  TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-second
delay Theminimumfadeanddelaytimeis0seconds Themaximumfadeanddelaytimeis4hours Forshadeoutputs,
theFadeparameterhasnoeffect(sinceshadeshavexedspeeds)butitisrequiredwhenspecifyinganoptionaldelay
HomeWorks QS (continued)
System Commands (continued)
OUTPUTCommands(continued)