Installation Manual
52
Lutron integration protocol
SHADEGRP Command Formats
SHADEGRP Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)ShadeGroupLevel 1 Level
1
=0–100or0 00 –100 00
Delay
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising
3
2 None
Set(#)StartLowering
3
3 None
Set(#)StopRaisingorLowering 4 None
Set(#)orGet(?)CurrentPreset 6 PresetNumber
4
= 0 – 3 0
Set(#)TiltLevel 14 Level
5
=0–100
6
or0 00–100 00
6
Fade
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Delay
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Set(#)LiftandTiltLevels 15 Lift
5
=0–100or0 00 –100 00
Tilt
5
=0–100
6
or0 00–100 00
6
Fade
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Delay
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaisingTilt
3
16 None
Set(#)StartLoweringTilt
3
17 None
Set(#)StopRaisingorLoweringTilt
3
18 None
Set(#)StartRaisingLift
3
19 None
Set(#)StartLoweringLift
3
20 None
Set(#)StopRaisingorLoweringLift
3
21 None
Get(?)HorizontalSheerShadeRegion 28 Lift=0
Tilt=1
NOTES
1 TheFadeandDelaytimeareoptional Forshades,theFadeparameterhasnoeffect(sinceshadeshavexedspeeds)
butitisrequiredwhenspecifyinganoptionaldelay Whennotused,thesystemwilluseazero-seconddelay The
minimumfadeanddelaytimeis0seconds Themaximumfadeanddelaytimeis4hours
2 Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifadelaytimeisspecied
as1 45seconds,avalueof1 25secondswillbeused
3 WhenaRaise/Lowercommandisissued,theshadegroup’slevelwillcontinuetogotowardsopen/closeuntilaStop
commandisreceived
4 Preset0istheOpenPresetandPreset30istheClosedPreset
5 TheLevelisacceptedasapercentage,where100%isfullyopenand0%isfullyclosed
6 50forHorizontalSheerBlinds
HomeWorks QS (continued)
System Commands (continued)
SHADEGRPCommands
Use “SHADEGRP Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#SHADEGRP,2,ActionNumber,Parameters
Continuedonnextpage…