Installation Manual

2
Lutron integration protocol
About Integration (continued)
Command and Control Examples
1) Thiscommandsetsadimmer(1)levelto75%witha1minuteand30secondfadetime 
#OUTPUT,1,1,75,01:30<CR><LF>
Command Integration ID Command-specific fields
ActionNumber Level FadeTime
#OUTPUT 1 1 75 01:30
2) Thiscommandpressesbuttonnumber1ofakeypad(2) 
#DEVICE,2,4,3<CR><LF>
Command Integration ID Command-specific fields
ComponentNumber ActionNumber
#DEVICE 2 4 3
Query Examples
3) Thiscommandrequeststheoutputlevelforadimmer(3) 
?OUTPUT,3,1<CR><LF>
Command Integration ID Command-specific fields
Action
?OUTPUT 3 1
Monitoring Examples
4) Whenausermakesachangetoadimmerlocally,thefollowingcommandresponsewouldbesent
outfromthesystemorwhenrequestedbythecommandinExample3above Thiscommand
responseexampleshowsthelocaldimmer(3)levelwaschangedto90% 
~OUTPUT,3,1,90.00<CR><LF>
Command Integration ID Command-specific fields
Action Level
~OUTPUT 3 1 90 00