Installation Manual

64
Lutron integration protocol
OUTPUT Command Format
OUTPUT Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)OutputLevel 1 Level
1
=0–100or0 00 –100 00
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising
4
2 None
Set(#)StartLowering
4
3 None
Set(#)StopRaisingorLowering
4
4 None
Set(#)orGet(?)FlashFrequency 5 Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)CCOPulseTime 6 Pulse
5
timein:SS ss
3
,SS,MM:SS,orHH:MM:SS,
orDelay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)TiltLevel 9 Tiltlevelin%=0 00–100
6
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)LiftandTiltLevels 10 Lift
1
=0–100or0 00 –100 00
Tilt
1
=0–100
6
or0 00–100 00
6
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaisingTilt 11 None
Set(#)StartLoweringTilt 12 None
Set(#)StopRaisingorLoweringTilt 13 None
Set(#)StartRaisingLift 14 None
Set(#)StartLoweringLift 15 None
Set(#)StopRaisingorLowringLift 16 None
Get(?)HorizontalSheerShadeRegion 28 Regions:0=Lift,1=Tilt
NOTES
1  TheLevel/Lift/Tiltistakenasapercentage
2  TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-second
delay Theminimumfadeanddelaytimeis0seconds Themaximumfadeanddelaytimeis4hours Forshadeoutputs,
theFadeparameterhasnoeffect(sinceshadeshavexedspeeds)butitisrequiredwhenspecifyinganoptionaldelay
3  Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifafadetimeisspecied
as1 45secondsavalueof1 25secondswillbeused
4  WhenaRaise/Lowercommandisissued,theoutput’slevelwillcontinuetogotowardshighend/lowenduntilaStop
commandisreceived 
5  Thedefaulttimeisonesecond
6  50forHorizontalSheerBlinds
myRoom plus (continued)
System Commands
OUTPUTCommands
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT
1
,2,ActionNumber,Parameters
NOTE
1  OUTPUTcommandscanbeusedtocontrolsystemlightingzones,individualshades,andcontactclosedoutputs
Assembled in U.S.A.