Installation Manual

69
Lutron integration protocol
myRoom plus (continued)
System Commands (continued)
SYSVARCommands
SYSVAR Command Formats
SYSVAR Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)thestate
ofagivenvariable
1 Statenumber
Example SYSVAR Messages
Operation Command String
Execute: #SYSVAR,IntegrationID,ActionNumber,Parameters
Setthevariablestatetothethirdstate #SYSVAR,2,1,3<CR><LF>
Query:?SYSVAR,IntegrationID,ActionNumber
Whatisthestateofthevariable? ?SYSVAR,2,1<CR><LF>
Response:~SYSVAR,IntegrationID,ActionNumber,Parameters
Thevariableisinthethirdstate ~SYSVAR,2,1,3<CR><LF>
Assembled in U.S.A.
50015757 Rev. A
GCU-HOSP
Guestroom Control Unit
+ 44.(0)20.7680.4481
+ 1.800.523.9466
lutron.com
243C IND. CONT. EQ.
IEC PELV/NEC Class 2
®
Use “SYSVAR Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#SYSVAR,2,ActionNumber,Parameters