Lutron integration protocol
INTEGRATION ID Command-specific fields
Action NumbersandParameters:
Description Action Number Parameters
Get(?)IntegrationIDforaSerial
Number
1
1 SerialNumber=8characterHEXserialnumberofthedevice
Get(?)InfofromID
1
3 IntegrationID
Note:Ifthiseldisleftblank,allintegrationIDswillbeprinted
Example INTEGRATION ID Commands
Operation Command String
Query: ?INTEGRATIONID,ActionNumber,Parameters
GettheIntegrationIDforaserialnumber ?INTEGRATIONID,1,5678EFEF<CR><LF>
Response: ~INTEGRATIONID,ActionNumber,Parameters
GettheIntegrationIDforaserialnumber ~INTEGRATIONID,1,5678EFEF,1<CR><LF>
Query: ?INTEGRATIONID,ActionNumber,Parameters
GetinformationaboutanIntegrationID
command
?INTEGRATIONID,3,1<CR><LF>
Response: ~INTEGRATIONID,ActionNumber,Parameters
GetinformationaboutanIntegrationID
command
~INTEGRATIONID,3,1,DEVICE,5678EFEF<CR><LF>
myRoom plus (continued)
System Commands (continued)
INTEGRATIONIDCommands
INTEGRATION ID Command Formats
Use “INTEGRATIONID Command-specific fields” tables
to complete these command fields.
Operation
Command
?INTEGRATIONID,ActionNumber,Parameters
Continuedonnextpage…