Installation Manual

79
Lutron integration protocol
Devices (continued)
Energi Savr Node QS for DALIR
HomeWorks QS / myRoom Power Module for DALIR (continued)
DEVICECommands
iPhoneandiPodToucharetrademarksofApple,Inc ,registeredintheU S andothercountries
V
D E
Test
Power
Hi Temp
Ethernet
DALI 1 DALI 2
IR
Photo
Com
20 V
20 V
Com
MUX
MUX
24 V
COM
Occ
IR
Photo
Occ
Energi Savr Node QS
QSNE-2DAL-D
230 V~ 50/60 Hz 100 mA
www.lutron.com
+44.(0)20.7680.4481
L N
1 1 2 2
3
3 4 4
QS
8 mm
0,5 Nm
N1771
Z096
DEVICE Command Formats
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE,5,ComponentNumber,ActionNumber,Parameters
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Zone1–Zone32
1,2,3
301–332 SetorGetLightLevel,Raise,Lower,Stop
Area1–Area32
1,3
401–432 SetorGetScene,SetLightLevel,Raise,Lower,Stop
OccupancySensors1–4 151– 154 Report(~)Occupied
Report(~)Unoccupied
NOTES
1  ZonesandareasarecreatedandconguredusingtheLutronESNCongurationToolonaniPhone oriPod Touch mobile
device,theQuantumQ-DesignTool,theHomeWorksQSLutronDesigner,orthemyRoomLutronDesigner Onlythose
areasandzonesthathavebeenconguredusingoneofthesetoolsareaccessiblethroughintegration
2  AssignedzonescanbegivenanindividualIntegrationIDandcontrolledusingthe#OUTPUTcommand Formoredetails
onsettingtheoutputIntegrationIDofazonecomponent,seetheIntegrationAccessPointsectionofthesystemthat
containstheESN
3  WhentheESNispartofaQuantumsystem,thenthe#AREAand#OUTPUTcommandsfoundintheQuantum“System
Commands”sectionofthisintegrationdocumentshouldbeused
Action Numbers and Parameters:
Action Action Number Parameters
Report(~)Occupied 3 None
Report(~)Unoccupied 4 None
Set(#)orGet(?)CurrentScene 7 Scene
Set(#)SceneSave
1
12 Scene
Set(#)orGet(?)LightLevel 14 Level=0–100or0 00–100 00
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
(QSStandalonefade:maximum90seconds)
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
(QSStandalonedelay:maximum4hours)
Set(#)SceneLock
4
16 0=Off;1=On
Set(#)SequenceState
4
17 0=Off;1=SequencethroughScenes1–4;
2=SequencethroughScenes5–16
Set(#)StartRaising 18 None
Set(#)StartLowering 19 None
Set(#)StopRaisingorLowering 20 None
NOTES
1  AvailableonlywithEnergiSavrNodermware>6 x
2  TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-seconddelay
3  Fractionalseconds“SS ss”willberoundeddowntothenearestquarter-second Forexample,ifafadetimeisspecied
as1 31seconds,avalueof1 25secondswillbeused
4  QSStandaloneonly
Continuedonnextpage…