Installation Manual
82
Lutron integration protocol
Devices (continued)
Energi Savr Node QS with EcoSystem
HomeWorks QS / myRoom Power Module with EcoSystem
(continued)
DEVICECommands
1
DEVICE Command Formats
iPhoneandiPodToucharetrademarksofApple,Inc ,registeredintheU S andothercountries
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE,5,ComponentNumber,ActionNumber,Parameters
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
OccupancySensors1–4 136–139 Report(~)Occupied,Report(~)Unoccupied
Loop1BallastOccupancySensors 140–203 Report(~)Occupied,Report(~)Unoccupied
Loop2BallastOccupancySensors 204–267 Report(~)Occupied,Report(~)Unoccupied
Zone1–Zone100
1,2,3
1001–1100 SetorGetLightLevel,Raise,Lower,Stop
Area1–Area100
1,3
1201–1300 SetorGetScene,SetLightLevel,Raise,Lower,Stop
NOTES
1 ZonesandareasarecreatedandconguredusingtheLutronESNCongurationToolonaniPhone oriPod Touch mobile
device,theQuantumQ-DesignTool,theHomeWorksQSLutronDesigner,orthemyRoomLutronDesigner Onlythose
areasandzonesthathavebeenconguredusingoneofthesetoolsareaccessiblethroughintegration
2 AssignedzonescanbegivenanindividualIntegrationIDandcontrolledusingthe#OUTPUTcommand Formoredetails
onsettingtheoutputIntegrationIDofazonecomponent,seetheIntegrationAccessPointsectionofthesystemthat
containstheESN
3 WhentheESNispartofaQuantum,HomeWorksQSormyRoomplussystem,the#AREAand#OUTPUTcommands
foundintheQuantum“SystemCommands”sectionofthisintegrationdocumentshouldbeused
Action Numbers and Parameters:
Action Action Number Parameters
Report(~)Occupied 3 None
Report(~)Unoccupied 4 None
Set(#)orGet(?)CurrentScene 7 Scene
Set(#)SceneSave
1
12 Scene
Set(#)orGet(?)LightLevel 14 Level=0 –100or0 00 –100 00
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)SceneLock
4
16 0=Off;1=On
Set(#)SequenceState
4
17 0=Off;1=SequencethroughScenes1–4;
2=SequencethroughScenes5–16
Set(#)StartRaising 18 None
Set(#)StartLowering 19 None
Set(#)Stop
RaisingorLowering
20 None
NOTES
1 AvailableonlywithEnergiSavrNodeFirmware>6 x
2 TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-seconddelay
3 Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifafadetimeisspecied
as1 31seconds,avalueof1 25secondswillbeused
4 QSStandaloneonly
NOTE
1 NotSupportedinHomeWorksQS/myRoomplus
Continuedonnextpage…