Installation Manual

85
Lutron integration protocol
Devices (continued)
Energi Savr Node QS for 0 –10 V/Softswitch/Phase Adaptive
HomeWorks QS / myRoom Power Module for 0 –10 V/
Softswitch / Phase Adaptive (continued)
DEVICECommands
1
DEVICE Command Formats
iPhoneandiPodToucharetrademarksofApple,Inc ,registeredintheU S andothercountries
H
M
L
QSNE-4A-D
DIN Rail Power Module
230 V~ 50 / 60 Hz 10 A
www.lutron.com
+44.(0)20.7702.0657
Input
S1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
Def
Option
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE,5,ComponentNumber,ActionNumber,Parameters
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Zone1–Zone4
1,2,3
5 – 8 SetorGetLightLevel,Raise,Lower,Stop
Area1–Area4
1,3
10–13 SetorGetScene,SetLightLevel,Raise,Lower,Stop
OccupancySensor1–4 34–37 Report(~)Occupied,Report(~)Unoccupied
OccupancySensor1–2 34–35 Report(~)Occupied,Report(~)Unoccupied
NOTES
1  ZonesandareasarecreatedandconguredusingtheLutronESNCongurationToolonaniPhone oriPod Touch mobile
device,theQuantumQ-DesignTool,theHomeWorksQSLutronDesigner,orthemyRoomLutronDesigner Onlythose
areasandzonesthathavebeenconguredusingoneofthesetoolsareaccessiblethroughintegration
2  AssignedzonescanbegivenanindividualIntegrationIDandcontrolledusingthe#OUTPUTcommand Formoredetails
onsettingtheoutputIntegrationIDofazonecomponent,seetheIntegrationAccessPointsectionofthesystemthat
containstheESN
3  WhentheESNispartofaQuantum,HomeWorksQSormyRoomplussystem,the#AREAand#OUTPUTcommands
foundintheQuantum“SystemCommands”sectionofthisintegrationdocumentshouldbeused
Action Numbers and Parameters:
Action Action Number Parameters
Report(~)Occupied 3 None
Report(~)Unoccupied 4 None
Set(#)orGet(?)CurrentScene
1
7 Scene
Set(#)SceneSave
2
12 Scene
Set(#)orGet(?)LightLevel 14 Level=0–100or0 00–100 00
Fade
3
in:SS ss
4
,SS,MM:SS,orHH:MM:SS
Delay
3
in:SS ss
4
,SS,MM:SS,orHH:MM:SS
Set(#)SceneLock
1
16 0=Off;1=On
Set(#)SequenceState
1
17 0=Off;1=SequencethroughScenes1–4;
2=SequencethroughScenes5–16
Set(#)StartRaising 18 None
Set(#)StartLowering 19 None
Set(#)StopRaisingorLowering 20 None
NOTES
1  QSStandaloneonly
2  AvailableonlywithEnergiSavrNodeFirmware>6 x
3  TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-seconddelay
4  Fractionalseconds“SS ss”willberoundeddowntothenearestquarter-second Forexample,ifafadetimeisspecied
as1 31seconds,avalueof1 25secondswillbeused
NOTE
1  NotSupportedinHomeWorksQS/myRoomplus
Continuedonnextpage…