Installation Manual

86
Lutron integration protocol
H
M
L
QSNE-4A-D
DIN Rail Power Module
230 V~ 50 / 60 Hz 10 A
www.lutron.com
+44.(0)20.7702.0657
Input
S1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
Def
Option
OUTPUT Command Format
OUTPUT Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)ZoneLevel 1 Level=0–100or0 00–100 00
Fade
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
(QSStandalonefade:maximum4hours)
Delay
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
(QSStandalonedelay:maximum4hours)
Set(#)StartRaising 2 None
Set(#)StartLowering 3 None
Set(#)
StopRaisingorLowering
4 None
NOTES
1  TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-seconddelay
2  Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifafadetimeisspecied
as1 31secondsavalueof1 25secondswillbeused
Example OUTPUT Commands
Operation Command String
Execute: #OUTPUT,IntegrationID,ActionNumber,Parameters
Setdimmerto75%witha1min30secfade #OUTPUT,1,1,75,01:30<CR><LF>
StartRaisingzonelevel #OUTPUT,1,2<CR><LF>
StopRaising/Loweringzonelevel #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT,IntegrationID,ActionNumber
Whatisthestateoftheoutput? ?OUTPUT,1,1<CR><LF>
Response
1
: ~OUTPUT,IntegrationID,ActionNumber,Parameters
Outputlevelissetto90% ~OUTPUT,1,1,90.00<CR><LF>
NOTE
1  Thesystemwillreportthetargetlevelofadimmerwhileitisfadingfromoneleveltoanother 
Theactuallevelisnottransmittedwhiledimmingbetweenlevels 
Example:Ifthe“OverSink”(IntegrationID-1)dimmerisat20%andisthencommandedtogoto100%bysending
#OUTPUT,1,1,100,theresponsefromthesystemwillbe~OUTPUT,1,1,100.00
Devices (continued)
Energi Savr Node QS for 0 –10 V/Softswitch/Phase Adaptive
HomeWorks QS / myRoom Power Module for 0 –10 V/
Softswitch / Phase Adaptive (continued)
OUTPUTCommands
Operation
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Command
Integration ID (example)
#OUTPUT,1,ActionNumber,Parameters