Installation Manual

88
Lutron integration protocol
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Zone1Zone4
1,2
1 – 4 SetorGetLightLevel,Raise,Lower,Stop
NOTES
1  AssignedzonescanbegivenanindividualIntegrationIDandcontrolledusingthe#OUTPUTcommand Formoredetails
onsettingtheoutputIntegrationIDofazonecomponent,seetheIntegrationAccessPointsectionofthesystemthat
containstheQSMotorModule
2  WhentheQSMotorModuleispartofaQuantumsystem,thenthecommandsfoundintheQuantum“System
Commands”sectionofthisintegrationdocumentshouldbeused
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)LightLevel 14 Level=0–100or0 00–100 00
1
Fade
2
in:Alwaysuse0
Delay
3
in:SS ss
4
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising 18 None
Set(#)StartLowering 19 None
Set(#)StopRaisingorLowering 20 None
NOTES
1  Settingthelevelto0%willcausetheoutputtotravelintheCloseddirection;settingthelevelto100%willcausethe
outputtotravelintheOpendirection;settinganylevelfrom1–99%willbeignoredbytheoutput Queryingitslevelwill
report0or100%,basedonthelastdirectionitmoved
2  FadeisnotavailableforMotorLoadsbecausetheymoveataconstantrate Theparametermustbeentered,butis
ignored
3  Thedelaytimeisoptional Whennotused,thesystemwilluseazero-seconddelay
4  Fractionalseconds“SS ss”willberoundeddowntothenearestquarter-second Forexample,ifafadetimeisspecied
as1 31seconds,avalueof1 25secondswillbeused
DEVICE Command Format
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE,5,ComponentNumber,ActionNumber,Parameters
Devices (continued)
Energi Savr Node QS for Motor Module
HomeWorks QS / myRoom Power Module for Motor Module
(continued)
DEVICECommands
Continuedonnextpage…