Installation Manual
89
Lutron integration protocol
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)orGet(?)ZoneLevel 1 Level=0or100 00
1
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
4
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising 2 None
Set(#)StartLowering 3 None
Set(#)StopRaisingorLowering 4 None
Report(~)TravelTimeRemaining
5
17 Traveltimeinseconds:0–255
Set(#)MotorJogRaise
6
18 None
Set(#)MotorJogLower
6
19 None
Set(#)Motor4-StageJogRaise
6
20 None
Set(#)Motor4-StageJogLower
6
21 None
NOTES
1 Settingthelevelto0%willcausetheoutputtotravelintheCloseddirection;settingthelevelto100%willcausethe
outputtotravelintheOpendirection;settinganylevelfrom1–99%willbeignoredbytheoutput Queryingitslevelwill
report0or100%,basedonthelastdirectionitmoved
2 FadeisnotavailableforShadesbecausetheymoveataconstantrate Theparametermustbeentered,butisignored
3 Fractionalseconds“SS ss”willberoundeddowntothenearestquarter-second Forexample,ifadelaytimeisspecied
as1 45seconds,avalueof1 25secondswillbeused
4 Thedelaytimeisoptional Whennotused,thesystemwilluseazero-seconddelay Theminimumdelaytimeis0 25
seconds;themaximumdelaytimeis4hours
5 Ifthetraveltimeofamotorisgreaterthan255seconds,theunitwillreport255untilthetraveltimedropsbelowthat
value
6 NotsupportedinQSStandalone
OUTPUT Command Format
Devices (continued)
Energi Savr Node QS for Motor Module
HomeWorks QS / myRoom Power Module for Motor Module
(continued)
OUTPUTCommands
Operation
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Command
Integration ID (example)
#OUTPUT,3,ActionNumber,Parameters