Lutron integration protocol
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)orGet(?)ZoneLevel 1 0–100or
0 00–100 00
SS ss
1
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising 2 None
Set(#)StopLowering 3 None
Set(#)Stop
Raisingor
Lowering
4 None
Set(#)Flashing
2
5 SS ss
1
,SS,MM:SS,orHH:MM:SS
Set(#)PulseTime 6 SS ss
1
,SS,MM:SS,orHH:MM:SS
Set(#)MotorJogRaise 18 None
Set(#)MotorJogLower 19 None
Set(#)Motor4-StageJog
Raise
20 None
Set(#)Motor4-StageJog
Lower
21 None
NOTES
1  Fractionsareroundeduptotheclosest¼second
2  Tostopadimmerfromashing,sendittoavalidlevel(action1)
OUTPUT Command Format
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT,6,ActionNumber,Parameters
Devices (continued)
Remote Power Module (continued)
OUTPUTCommands