Cut Sheet

10
2. Receptacle Components Lutron Satin Colors Style
a. All receptacles shall be UL Listed, CSA and NOM approved.
b. Receptacles shall be two pole, three wire ground and rated
for 15A at 125VAC. All receptacles shall be NEMA
conguration type 5-15R.
c. Ground-fault interrupter receptacles shall be Lutron Satin
Colors style with two-pole, three-wire ground and rated 15A
at 125VAC Conguration shall be of the duplex type with
rectangular NEMA WD-6 design. Receptacles shall have a 5
milliampere ground-fault trip level with "test" and "reset"
buttons.
3. Telephone Jack and Cable TV Jack Components Lutron Satin
Colors Style
a. Contractor shall provide an appropriate barrier (partition) to
isolate jack from high-voltage wiring when ganged with a
dimmer, fan-speed control, switch, or receptacle. This
complies with NEC Articles 800-3 and 820-13.
b. Telephone jack shall be designed to mate with standard
4- or 6-conductor modular jacks, and be compatible with
2, 4, or 6 conductor lines. Telephone jacks shall meet
FCC Part 68, paragraph F standards to ensure compatibility
with U.S. telephone systems.
c. Cable TV jacks shall be the coaxial type, designed for use
with standard 75-Ohm cables.
C. Wallplates Lutron Satin Colors Style
1. Wallplates shall be manufactured from durable polycarbonate
plastic with matte nish, and shall attach to the basic
components without using exposed hardware or screws.
2. Multigang wallplates shall provide a continuous, seamless cover
for up to six-ganged decorator-style control and accessory
combinations with no exposed hardware or screws.
3. Multigang wallplates shall include an adapter plate for proper
device alignment and wallplate attachment.
4. Control, accessory and wallplate proles shall not exceed
.30 inches from wall surface to faceplate front surface.
5. To ensure a precise color match between all plastic parts,
color variation of any matte nish control or wallplate shall
not exceed a delta E of 1, CIE L*a*b* color units, as dened in
ASTM E 308-99.
6. Visible parts of dimmers, switches, standard receptacles,
cable jacks or any wallplate shall exhibit ultraviolet stability when
tested with multiple actinic light sources as dened in ASTM
D4674-89.
2.03 S
OURCE
Q
UALITY
C
ONTROL
A. All dimming controls shall be 100% function tested at the time of
manufacture. Statistical sampling plan shall not be acceptable.
c. Dimmers shall have a resettable overload protection that
automatically shuts off when dimmer capacity is exceeded.
Protection methods that are non-resettable or require the
device to be removed from the wall shall not be acceptable.
d. Dimmers shall be designed to withstand a short, per UL
1472 section 5.10, between load hot and either neutral or
ground without damage to the dimmer.
e. Dimmers shall have a high-end of no less than 90% of line
voltage.
4. Magnetic Low Voltage (MLV) Transformer Dimmers
a. Provide MLV dimmers for direct control of up to 1000 volt
amps of electronic low voltage load.
b. Dimmers shall contain circuitry specically designed to
control and provide a symmetrical AC waveform to the input
of magnetic low voltage transformers per UL1472 section
5.11.
c. Dimmers shall not cause a magnetic low voltage
transformer to operate above the transformers rated
operating current or temperature.
d. Dimmer shall be capable of operating in either 3-way switch
location.
5. Fluorescent Dimming Ballast Dimmers
a. Provide Fluorescent dimmers for direct control of uorescent
dimming ballasts up to the manufacturers specied rating.
b. Dimmers shall be designed to operate the following ballasts.
Dimmers and ballasts shall be produced by the same
manufacturer to ensure proper ballast/control compatibility:
1) Hi-lume
® Architectural Dimming Ballasts (1% 3-wire)
2) Hi-lume
® CompactTM Lamp Dimming Ballasts
(5% 3-wire)
3) Eco-10
TM Lighting Management Dimming Ballasts
(10% 3-wire)
4) Tu-Wire High Performance Dimming Ballasts
(5% 2-wire)
6. Remote dimming modules for high power loads
a. Where lighting loads exceed the full rated capacity of single
dimmers, provide a Diva Satin Colors incandescent dimmer
driving high power modules. High power module and
dimmer shall be from the same manufacturer to ensure
compatibility.
b. High power modules shall be remotely mounted.
c. High power module shall be rated and UL listed for control of
incandescent, magnetic low voltage, electronic low voltage,
uorescent, and neon/cold cathode loads in increments of
2,000 Watts up to 30,000 Watts.
7. Fan-Speed Controls:
a. Fan-speed controls shall be UL Listed, CSA and NOM
approved, Lutron Diva Satin Colors style.
b. Quiet fan-speed model shall provide three speed settings
with paddle providing preset on and off.
c. Quiet fan-speed control shall provide single-pole/3-way
control of one paddle fan (1.5A max.).
B. Accessories Lutron Satin Colors Style
1. Switch Components Lutron Satin Colors Style
a. Switches shall provide on/off control of any 120/277 VAC
load up to 15A. Switches shall be UL Listed as general-use
AC switches, Lutron Satin Colors style.
b. Switches shall be available in single-pole, 3-way and 4-way
congurations.
Have Questions? Call the Lutron Hotline 800-523-9466
To order—Call Lutron Customer Service 610-282-3800
Controls