Installation Guide
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® GFCI – Tamper Resistant, Self-Testing Receptacles
369964a 2 08.13.15
Specifications
Regulatory Approvals
• Meets UL 943 Class A GFCIs and UL 498 for
Receptacles
• Complies to NEC, CEC & OSHA, UL File E-41978,
CSA File LR-24886
• UL Listed
• CSA Certified
• NOM Certified
• UL 943 Dust Test: Meets performance requirement
section 6.20 UL 943 GFCI
Power
• 15 A & 20 A, 125 V~ (102 V~ – 132 V~) 60 Hz
• Exceeds immunity level of 0.5 V over a frequency
range of 150 kHz to 230 MHz
Electrical
• Trip Level: 4 – 6 mA
• Trip Time: .025 seconds (nominal)
• Frequency: 60 Hz
• Max Interruption: 10,000 A
Environmental
• Operating Temperature: -35 °C to 66 °C
(-30 °F to 150 °F)
• Maximum Humidity: 95%
Emissions
• Compliant for radiated emissions 30 – 1000 MHz
• Compliant for conducted emissions 150 kHz –
30 MHz
2