User's Manual
Table Of Contents
- 95 Series RFID System User’s Guide
- Table of Contents
- List of Figures
- Preface
- Introduction
- Reader R95 Installation and Connections
- Exciter E95 Installation and Connections
- Power Supply TRM95 Installation and Connection
- Configuration and Operation
- Before You Begin
- General Procedure Rules
- Setting Up the Reader/PC Connection
- Reader’s Power-up Sequence
- Learning Procedure (Optional)
- Resetting the Reader
- Checking the Reader’s Basic Parameters
- Setting Up the Exciter’s Address
- LF Transmitter Output
- Configuring the Reader
- Setting Up the Carrier Threshold
- Setting Up the Exciter’s Test-Tag
- Setting Up the Real Time Clock
- Configuring the Reader’s Application Parameters
- Configuring the Reader’s Network Parameters
- Storing the Reader’s Configuration
- Reader - Final Setup
- 95 Series RFID System - Final Test
- Programming and Testing the Transponder T95
- Troubleshooting
- Specifications
- Transponder T95 Messages
- Excitation Modes
- Reader Software Upgrade Procedure
- Glossary
- Index
Configuring the Reader
5-8 Configuration and Operation
For example, Lyngsoe recommends the following parameter values for the
Conditional Switching AC mode (CSAC) for the IPC installation:
RCS=Y; RES=Y; REM=C; RET=A; HCC=8; HCS=7; HE0=18; HE1=6
These parameters all have the default values.
8. Check the excitation field pattern as set in Step 7, by monitoring the TAP voltage.
For example, if the IPC’s CSAC mode was set and the Reader did not receive a
valid message, the TAP voltage has the following repetitive pattern: a carrier of
128.25 kHz modulated ON/OFF with 610Hz for 60 ms, followed by no signal for
180 ms.
9. Save the excitation mode set in Step 7, by typing:
:CONFIG:STORE <Enter>
:RESET <Enter>
10. Check the parameter values set in Step 7 again.
11. Check the auto-diagnostic feature, by typing:
:DAR=Y <Enter>
:TEST:EXCITER k <Enter>
where k is the decimal address (1, 2, 3, ...) of the Exciter that you want to test.
The response should be 00, followed by a number (between IP-2 and IP) of
messages from the Test Tag.
12. Turn off the excitation field again, by typing:
C<Enter>
13. Check the auto-diagnostic feature, by typing:
:TEST:EXCITER k <Enter>
The response should be C9.
14. Repeat Steps 1 to 13 (inclusive) for each Exciter that is connected to the Reader.
Configuring the Reader
The Reader’s basic configuration covers the following group of parameters:
• Data buffering/reporting configuration - Group D parameters
• Hardware configuration - Group H parameters
• Instrument generic configuration - Group I parameters
• Tag data reading configuration - Group R parameters
For more information on these parameters, see the 95 Series RFID System Reference
Guide and the 95 Series RFID System Technical Guide.