User's Manual
Table Of Contents
- 95 Series RFID System User’s Guide
- Table of Contents
- List of Figures
- Preface
- Introduction
- Reader R95 Installation and Connections
- Exciter E95 Installation and Connections
- Power Supply TRM95 Installation and Connection
- Configuration and Operation
- Before You Begin
- General Procedure Rules
- Setting Up the Reader/PC Connection
- Reader’s Power-up Sequence
- Learning Procedure (Optional)
- Resetting the Reader
- Checking the Reader’s Basic Parameters
- Setting Up the Exciter’s Address
- LF Transmitter Output
- Configuring the Reader
- Setting Up the Carrier Threshold
- Setting Up the Exciter’s Test-Tag
- Setting Up the Real Time Clock
- Configuring the Reader’s Application Parameters
- Configuring the Reader’s Network Parameters
- Storing the Reader’s Configuration
- Reader - Final Setup
- 95 Series RFID System - Final Test
- Programming and Testing the Transponder T95
- Troubleshooting
- Specifications
- Transponder T95 Messages
- Excitation Modes
- Reader Software Upgrade Procedure
- Glossary
- Index
95 Series RFID System - Final Test
Configuration and Operation 5-15
If there is no unwanted transmission on the UHF channel, the Reader must
respond with a value lower than -95dBm for the HNL parameter. If not, refer to
Setting Up the Carrier Threshold on page 5-9.
c) Check and record the value for the existing Reader’s Carrier Threshold level, by
typing:
@r HTL<Enter>
The Reader should respond with the value for this parameter. For example,
HTL=95.
d) If the HNL level measured in Step b is lower than -95dBm, set the Reader’s
Carrier Threshold level again, by typing:
@r S<Enter>
or
@r :CONFIG:THRESHOLD<Enter>
The Carrier Threshold level setting is correct if the new HNL level displayed is
smallerthanorequaltotheleveldisplayedinStepc.Ifnot,checkforunwanted
transmission on the UHF channel. You should also refer to Chapter 4, Setup
Guidelines in the 95 Series RFID System Technical Guide.
3. Verify that an Exciter that is controlled by a Reader communicates with the Main
PC:
a) Delete all Tag records from the Reader’s buffer, by typing:
@r :DATA:PURGE<Enter>
b) Confirm that the Reader’s buffer is empty, by typing:
@r D<Enter>
or
@r :DATA:REPORT<Enter>
The Reader must report a Null value.
Note For an IPC application, the data structure conforms to the ANS.1 standard. If the
Reader’s buffer is empty, the Reader sends a Null value of $0500.InASCIIformat,
the Null value is {}.
c) Switch on the LF field, by typing:
@r B<Enter>
d) Send a Test Exciter command, by typing:
@r :TEST:EXCITER k<Enter>
where r is the Reader’s address and k is the Exciter’s address. The correct
Exciter’s response is 00.