S21 RFID System - Final Test
Configuration and Operation 5-17
The Reader must respond with the oldest record sent by the Exciter k’s Test-Tag, in the format
set by the DHX parameter. For more information on this parameter, refer to the 95 Series RFID
System Reference Guide.
Note If the equipment is connected to the Lyngso Industri EDECS Module all setup parameters are set
automatically.
For an IPC application, the Reader’s Tag Record Buffer contains 13-15 identical messages sent by
the Exciter Test Tag in ANS.1 format. To read all messages, you have to repeat the commands:
@r D<Enter>
@r E<Enter>
until you get the Null value $0500.
f) Empty the Reader’s Tag record buffer, by typing:
@r :DATA:PURGE<Enter>
g) Confirm that the Reader’s buffer is empty, by typing:
@r :D<Enter> or @r :DATA:REPORT<Enter>
The Reader must report the Null value ($0500) in ANS.1 format.
4. Repeat Step 3 for all Exciters controlled by the Reader r.
5. Repeat Steps 1 to 4 for all Readers that are connected to the same PC.