Operation Manual
LUNA 1000DH/CL/CR/DC - 1150DH - 1300DH/CL/CR/DC - 1600DH/CL/CR/DC GOLD - GAS
12
Pic. 5 ROOF EXIT with 90° bends
CAUTION : if the vertical lenght is over 3 meter longer than the horizontal lenght, you will
need to place a reduction ring of
Ø 60.
Appliance
Ø 150/100 and Ø 200/130
1000 / 1150
1300 / 1600
for each 90° bend substract 1 m horizontaly or add 1 m verticaly.
1000 / 1150
1300 / 1600
for each 45° / 30° / 15° bend substract 0,5 m horizontaly or add 0,5 m
verticaly.
Pic. 5
Fig. 5 ROOF EXIT with 90° bends
Ø 150/100
WITH REDUCTION USVK13 oN APPLIANCE
Aplliance A (min) B (max) C (min) (A+B+C )max
1000 DH / CL / CR / DC
1,25 m A+C B-A-1m 17m
1150 DH
1,25 m A+C B-A-1 16m
1300 DH / CL / CR / DC
1,25 m A+C B-A-0,5 15m
1600 DH / CL / CR / DC
1,25 m A+C-1m B-A 14m
Ø 200/130
without reduction
Appliance A (min) B (max) C (min) (A+B+C )max
1000 DH / CL / CR / DC
1 m (A+C) + 8m B-A-9m 19m
1150 DH
1 m (A+C) + 7m B-A-8m 18m
1300 DH / CL / CR / DC
1 m (A+C) + 6m B-A-7m 17m
1600 DH / CL / CR / DC
1 m (A+C) + 3m B-A-4m 17m
DH = Double Face CL = Corner Left CR=Corner Right DC = Double Corner
DH = Double Face CL = Corner Left CR=Corner Right DC = Double Corner
WITH REDUCTION USVK13
oN APPLIANCE