Operation Manual
INSTRUCTION FOR INSTALLATION AND USE - LUNA 700-1000-1150-1300-1600-1900H GOLD - GAS
12
Pic. 5 ROOF EXIT with 90° bends
CAUTION : if the vertical lenght is over 3 meter longer than the horizontal lenght, you will
need to place a reduction ring of
Ø 60.
Appliance
Ø 150/100 and Ø 200/130
700H / 1000H / 1150H
1300H / 1600H /1900H
for each 90° bend substract 1 m horizontaly or add 1 m verticaly.
700H/ 1000H / 1150H
1300H / 1600H/1900H
for each 45° / 30° / 15° bend substract 0,5 m horizontaly or add 0,5 m
verticaly.
Pic. 5 ROOF EXIT with 90° bends
Ø 150/100
WITH REDUCTION USVK13 ON APPLIANCE
Aplliance A (min) B (max) C (min) (A+B+C )max
700/1000 H
1,25* m A+C+0,5m B-A-0,5m 18m
1150 H
1,25* m A+C+0,5 B-A-0,5 17m
1300 H
1,25* m A+C B-A 16m
1600 H
1,25* m A+C-0,5m B-A+0,5m 16m
1900 H
1,25*m A+C-1m B-A+1m 14m
Ø 200/130
without reduction
Appliance A (min) B (max) C (min) (A+B+C )max
700H / 1000 H
1 m (A+C) + 8m B-A-9m 20m
1150 H
1 m (A+C) + 7m B-A-8m 19m
1300 H
1 m (A+C) + 6m B-A-7m 18m
1600 H
1 m (A+C) + 3m B-A-4m 18m
1900 H
1 m (A+C)+1m B-A-2m 16m
WITH REDUCTION USVK13
oN APPLIANCE