Operation Manual

INSTRUCTION FOR INSTALLATION AND USE - LUNA 700-1000-1150-1300-1600-1900H GOLD - GAS
39
Min. distance between appliance
and maconery : 4cm
X = inside measurement frame ( nished size )
Y = measurment from underneath 4th side frame till upper side frame above window
3 mm = thickness frame
2 mm = gap between frame and maconery
Apperture to make
L = X + 3mm + 3mm + 2mm + 2mm
H = Y + 2mm
Connecting Flex tubes
700H/ 1000H/1150H/1300H : 2x ( obliged)
1600H : 4 x ( obliged ) / 1900H : 6x (obliged)
Minimum distance to wich can be
mounted
Inlet convection: OBLIGED !
Min. 4cm
Example how to mount with a 4-sided frame
4-sided frame 3,5 - 7 or 10 cm
Two exible tubes can be connected to one
design grid ( 2 connections )
Min.
5mm
3
2
2
TYPE
X L Y H
700H 623 633 406 408
1000H/DH 923 933 406 408
1150H/DH 1073 1083 406 408
1300H/DH 1223 1233 406 408
1600H/DH 1523 1533 406 408
1900 H 1823 1833 406 408
550V/DV 473 483 906 908
850V/DV 773 783 666 668