8. Dew point Alarm
Designation
Options
Description
Dew point alarm
Disabled
Enabled
No function.
If the alarm function is activated an alarm in form of an object is sent when the defined dew point is
exceeded or fallen below.
Dew point alarm
advance
Without
1K to 5K
The dew point alarm can be initiated in advance with a defined offset.
Dew point alarm
hysteresis
(symmetrical)
Without hysteresis
Hysteresis
1 K to 5 K
No function.
If there is a change, the recent control value is sent.
Send dew point alarm
when change of status
Disabled
Enabled
No function.
Upon change of status dew point alarm is sent.
Send dew point alarm
cyclically
Disabled
Every minute once a day
No function.
Cyclic sending of the recent control value.
Type of telegram for dew
point alarm
Switching command
Priority
Percent
Byte
Scene
Definition of the type of telegram which is used.
value when
dew point alarm
Depending on the type of telegram
Definition of the value that is sent when the dew point alarm starts.
value at the end of dew
point alarm
Depending on the type of telegram
Definition of the value that is sent when the dew point alarm ended.