Instruction Manual
IT60SW5F
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-2433 P. 8 / 8
MODBUS I/O ASSIGNMENTS
■ MODBUS NODE ADDRESS 255
By sending Modbus query of node address 255 from Modbus/TCP master device connected to the unit, it is possible to perform
I/O operations for the unit’s lamps and buzzers. The unit sends a response to Modbus/TCP master device that sent the query.
ADDRESS DATA TYPE DATA
Coils (0X) 1 – 16 Digital Output (lamp, buzzer)
17 – 32 Reserved (unused)
Inputs (1X) 1 – 16 Digital Input (lamp, buzzer)
Input Registers (3X) ---- ---- Unused
Holding Registers (4X) ---- ---- Unused
■ OUTPUT DATA
015
Output 0
Output 1
•
•
•
Output 15
■ INPUT DATA
015
Input 0
Input 1
Input 15
•
•
•
Output 0
Lamp 1 0: Off, 1: On Input 0 Lamp 1 0: Off, 1: On
Output 1
Lamp 2 0: Off, 1: On Input 1 Lamp 2 0: Off, 1: On
Output 2
Lamp 3 0: Off, 1: On Input 2 Lamp 3 0: Off, 1: On
Output 3
Lamp 4 0: Off, 1: On Input 3 Lamp 4 0: Off, 1: On
Output 4
Lamp 5 0: Off, 1: On Input 4 Lamp 5 0: Off, 1: On
Output 5
Buzzer 0: Off, 1: Continuous Input 5 Buzzer 0: Off, 1: Continuous
Output 6
– – Input 6 – –
Output 7
– – Input 7 – –
Output 8
Lamp 1 0: Off, 1: Blinking Input 8 Lamp 1 0: Off, 1: Blinking
Output 9
Lamp 2 0: Off, 1: Blinking Input 9 Lamp 2 0: Off, 1: Blinking
Output 10
Lamp 3 0: Off, 1: Blinking Input 10 Lamp 3 0: Off, 1: Blinking
Output 11
Lamp 4 0: Off, 1: Blinking Input 11 Lamp 4 0: Off, 1: Blinking
Output 12
Lamp 5 0: Off, 1: Blinking Input 12 Lamp 5 0: Off, 1: Blinking
Output 13
Buzzer 0: Off, 1: Intermittent Input 13 Buzzer 0: Off, 1: Intermittent
Output 14
– – Input 14 – –
Output 15
– – Input 15 – –
Note: If “On” (Continuous) and “Blinking” (Intermittent) are set simultaneously for a single lamp (buzzer), “Blinking” is disabled.
■ MODBUS NODE ADDRESSES 1 – 247
When Modbus query of Modbus node address 1 to 247 is sent from Modbus/TCP master device connected to the unit, it is
transferred to a wireless device (child) that is connected to the unit via 900 MHz band wireless communication, then a re-
sponse from the wireless device (child) is sent to Modbus/TCP master device that sent the query.