Technical data

1/6
Feed-through terminal blocks WDU 70/95
Dimensions
Width/length/height (mm) with TS 32 Y
Width/length/height (mm) with TS 35 x 7.5 W
Insul. stripping length/clamping screw/setting acc. DIN 6911
VDE rated data. 0611 Part 1/8.92/IEC 947-7-1
Rated voltage/rated current/rated cross-section
Rated impulse voltage/pollution severity
Further technical data
Tightening torque range Nm
Torque setting with DMS2 electric screwdriver
Clampable conductor
“e” solid H07V-U mm
2
“mstranded H07V-R mm
2
“f” flexible H07V-K mm
2
“f flexible H07V-K and AEH DIN 46 228/1 mm
2
“f flexible H07V-K and AEH with Plastic.Col. mm
2
Gauge pin to 947-1 size
Cont. current rating of cross-connection 2 poles A
Cont. current rating of cross-connection multipole A
UL/CSA rated data
Voltage/current/conductor size UL
Voltage/current/conductor size CSA
Ordering data Version
hexagon socket 6 mm Wemid
hexagon socket 6 mm blue Wemid
hexagon socket 6 mm green Wemid
hexagon socket 6 mm Terminal block* 3 poles Wemid
hexagon socket 6 mm Terminal block* 4 poles Wemid
hexagon socket 6 mm Terminal block* 5 poles Wemid
Mains terminal block 3x beige. 1x blue. 1x green Wemid
Cross-connection
Auxiliary/control conductor terminal
Cover
yellow
white
Test plug
Fixing screw
for direct assembly
Hexagon key
Screwdriver for direct assembly 1 x 5.5 x 125
Marking tabs Print
Consecutive horizontal
Consecutive vertical
123456
Large size conductors no longer have to be
inserted into the clamping point with force;
they can simply be placed in the terminal
block.
For each terminal type, terminal block
variants consisting of three, four and five-
pole terminal blocks are available in
addition to the individual terminals. All
blocks are permanently screwed together
for additional rigidity.
Slots provided in the underside of the
terminal enable direct fitting. Terminal
blocks can be screwed directly to
mounting plates with 25 mm pitch.
Further advantages are:
• Constant force transmission by self-
adjusting connection resistance
• Random wiring direction
• Safe from finger-touch (VGB 4), even
with cross-connection fitted
Good distortion resistance
27/132/108
30 mm/M 8/S 6
1000 V/232 A/95 mm
2
8 kV/3
6...12
16
16…120
16…95
B 12
207
(3) 207
600 V/175 A/6…2/0 AWG
600 V/205 A/6…2/0 AWG
W Cat.No. Qty.
102460 10
102468 10
102465 10
Type Cat.No. Qty.
WQV 70/2 106350 5
WQV 70/3 106360 5
WZAD 70 106600 10
WAD 27
with warning tag 106286 10
WAD 27
no warning tag106296 10
PS 4 029960 20
Insertable in screw head of
connection system
M 6x16 106370 20
hex. key 040790
6 mm to DIN 6911
SD 903709
FW 5 047346
FS 5 047356
27/132/117
30 mm/M 8/S 6
1000 V/232 A/95 mm
2
8 kV/3
6...12
16
16…120
16…95
B 12
207
(3) 207
600 V/175 A/6…2/0 AWG
600 V/205 A/6…2/0 AWG
Y Cat.No. Qty.
103150 10
103158 10
103155 10
Type Cat.No. Qty.
WQV 70/2 106350 5
WQV 70/3 106360 5
WZAD 70 106600 10
WAD 27
with warning tag 106286 10
WAD 27
no warning tag106296 10
PS 4 029960 20
Insertable in screw head of
connection system
hex. key 040790
6 mm to DIN 6911
FW 5 047346
FS 5 047356
Open terminal cover,
remove screw terminal unit
Place conductor in terminal,
replace screw terminal unit
Close terminal cover,
tighten screw with hex key
Mounting rails, brackets, additional marking material and accessories