Mac Victor® Power Network (MVPN) Installation and Operating Instructions Mac Victor® Expand Your Power® Page 1 of 8
Mac Victor® Power Network (MVPN) Installation Instructions (Retrofits) 1. Determine which “critical circuit breakers” feed power to the remote receptacles and/or hard wired loads that are required to be tied into the power isolation and battery backup of the MVPN. This will typically be the POS network receptacles and related equipment, office computer, telephone system, security system, etc. 2. Remove the panelboard covers for the “critical circuit breakers”.
(Retrofit Installations - cont.) 14. Plug the POWERVAR UPM into the receptacle located on the right hand side exterior of the MVPN. Plug the cable coming from the top of the MVPN into one of the receptacles on the back of the POWERVAR UPM. 15. Turn on the POWERVAR UPM by pressing the “on/off” switch (right hand of front panel) and holding for several seconds until the row of 6 status indicator lights at the bottom of the bezel begins to illuminate.
Description of Operation • 120 VAC, 1φ input power (15A / 20A circuit) supplied to MVPN • Input power status light is illuminated • Power routed within MVPN to Normal / Bypass transfer switch • In Normal mode • Power routed from Normal/Bypass switch to the POWERVAR UPM • POWERVAR UPM conditions power and provides battery backup • 120 VAC, 1φ power conditioned UPM output is wired back to the MVPN • Output power status pilot light is illuminated • MVPN provides power conditioned, battery backup source to dedi
Where required by local Electrical AHJ Page 5 of 8
NUISANCE TRIPPING OF INPUT CIRCUIT BREAKER Some reports from field installations indicate that the 15 or 20 amp, single pole circuit breaker feeding main power to the Mac Victor® Power Network (MVPN) will sometimes trip off upon startup of the POWERVAR UPM. In all cases, factory testing has indicated that this problem is not associated with defects in the POWERVAR UPM.
POWERVAR UPM Details UPM Circuit Breaker (Each LED = 20%) (Each LED = 20%) Cooling Fan (Push to Start) Serial Comm Port Input Power from Mac Victor receptacle Input Power from Mac Victor receptacle Output Power receptacles to Mac Victor plug cable Output Power to Mac Victor plug cable Troubleshooting Tips Normal Operation “ON” “ON” * Both the “Input” & “Output” lights are “ON” * Switch to “Bypass” only when replacing the UPM * After replacing & starting up UPM, Switch back to “Normal” * When the Sw
Mac Victor® Expand Your Power® Mac Victor Power Fredericksburg, VA Phone: (540) 220-8116 Fax: (540) 242-7004 email: Bart@MacVictor.com www.MacVictor.com SM523 – 06/2005 - © 2005 POWERVAR, Inc.