Mac Victor 2.0 Installation and Operating Manual MVP-2KS / MVP-2KL (2 kVA rating) MVP-3KL (3 kVA rating) Victor an ultra quality power system provides centralized and wall mounted The The MacMac Victor 2.0 2.
Mac Victor 2.0 (Installation and Operating Manual) CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS …………………………………………………………………… 3 2 PRODUCT OVERVIEW …………………………………………………………………………………………………… 5 3 OPTIONS / ACCESSORIES …………………………………………………………………………………………… 8 4 INSTALLATION ……………………………………………………………………………………………………………… 9 5 STARTUP / OPERATION ……………………………………………………………………………………………… 14 6 MAINTENANCE/TROUBLESHOOTING …………………………………………………………………… 18 7 SPECIFICATIONS ………………………………………………………………………………………………………… 22 1.1 1.2 1.
1 - IMPORTANT SAFETY INSTRUCTIONS 1.1 Save these Instructions This manual contains important instructions and specifications for the Mac Victor 2.0 that should be followed during installation and maintenance. CAUTION: Risk of Personal Injury and Equipment Damage. Before attempting to install and power up the Mac Victor 2.0, carefully read this manual. Keep this manual with the Mac Victor 2.0 for future references. All service work must be done by qualified personnel.
• • • • • • • • • • • It is important to install the Mac Victor 2.0 in a location that provides adequate space above the unit for the later installation of the UPS. See the UPS Installation and Operating Manual for the critical dimensions. Both the Mac Victor 2.0 and the UPS should be positioned to insure that there is a minimum of 36 inches (3 feet) full front clearance for service and maintenance. The Mac Victor 2.
2 – PRODUCT OVERVIEW Figure 2.1 2.1 Operating Schematic The above Mac Victor 2.0 Operating Schematic provides a conceptual diagram of the system operation and does not represent an actual wiring diagram. See Section 2.4 for a Description of Operation. 2.
2.3 System Benefits • Provides clean and continuous power for critical electronic systems to minimize downtime and lost revenue associated with computer lockups, data losses, hardware failures and power outages. • Centralized, wall mounted design saves valuable floor space and is easier to maintain and manage. • Eliminates the need for all remote plug in battery backups, filters, power conditioners, and surge strips which saves under counter / desktop space.
2.5 Component Diagram Figure 2.2 2.6 Item numbers with Options Item numbers are comprised of one of the three Base Item Numbers with the addition of one or more Optional Item Suffixes added to the end of the Base Item Number. Multiple suffixes can be used for additional options. See Section 3 for more information about the available Options and other Accessory items. Example: 2kVA Mac Victor 2.
3 – OPTIONS / ACCESSORIES 3.1 Mac Victor 2.0 Options These Mac Victor 2.0 optional features are available with the MVP-2KS, MVP-2KL, and MVP-3KL base units. See complete part number listing in Section 2.6. -IG Suffix (Isolated Ground receptacle option) Integrated Isolated Ground Receptacles Option (-IG suffix) – includes 4 outlets and a 5th output circuit breaker. Mac Victor 2.
4 – INSTALLATION 4.1 Package Contents The packing box contains a Mac Victor 2.0, mounting hardware (wood stud mount only), a circuit polarity plug tester, safety outlet protector plugs (12), UPS strapping materials, and this Installation and Operating Manual. Carefully inspect all the contents. If any damage is visible immediately notify the carrier and the shipper. 4.2 Location Please refer to Section 1.3 of the Important Safety Instructions regarding installation.
4.4 Mounting Instructions • • • • • CAUTION – Improper installation can result in serious personal injury. Make sure the mounting surface can support a redundant weight factor five times the total weight of the equipment. If not, reinforce the structure before installation of the Mac Victor 2.0 CAUTION – Improper installation can result in equipment damage. The installer is responsible for verifying that the installation wall will safely support the combined load of the Mac Victor 2.
4.5 Wiring Diagram – Mac Victor 2.0 The below Mac Victor 2.0 Wiring Diagram provides the input and output wiring terminals for proper installation. The factory wiring and other wiring components are not shown for the sake of simplicity. Follow these wiring diagrams exactly and do not modify any factory wiring or other wiring components. Mac Victor 2.0 / Wiring Diagram Figure 4.
4.6 Wiring Diagram – Remote Power Off This Mac Victor 2.0 standard feature is for the manual shutdown of all Mac Victor 2.0 output power via an externally mounted Remote Power Off switch. Use only when required by the local Authority Having Jurisdiction (AHJ). Figure 4.
4.8 Wiring Diagram – Optional 5th Circuit IG Outlet and Optional Remote Off This Mac Victor 2.0 optional feature is for manual shutdown of just the optional Isolated Ground outlet power (left hand side of cabinet) only when required by the local Authority Having Jurisdiction (AHJ) and only in gasoline fueling applications. These special applications can have fueling data boxes plugged into the IG outlets that may need to be shut down during fueling emergencies.
5 – STARTUP / OPERATION 5.1 Power up of the Mac Victor 2.0 • WARNING: RISK OF ELECTRICAL SHOCK AND PERSONAL INJURY • Do not install the UPS until the startup of the Mac Victor 2.0 system is completed. 1. Turn off all input and output circuit breakers / Set the UPS Bypass Switch to the “Normal” position 2. Verify all the wiring connections are correct per Sections 4.5 – 4.8 3. Turn on the remote circuit breaker feeding the Mac Victor 2.
5.2 Installation and Strapping of the UPS • CAUTION: RISK OF PERSONAL INJURY AND EQUIPMENT DAMAGE. 1. The strapping of the UPS to the Mac Victor 2.0 shelf is strongly recommended before the UPS has been started up and is fully operational. Strapping requirements may vary for different localities so consult with the local Authority Having Jurisdiction (AHJ) for specific strapping requirements and / or materials. 2. The Mac Victor 2.
5.3 Power Up of the UPS 1. WARNING: RISK OF ELECTRICAL SHOCK AND PERSONAL INJURY 2. Consult the accompanying UPS Manual for the approved procedures for installing and powering up the UPS 3. Insert the UPS Plug Assy into the MV Power Receptacle on the right hand side of the enclosure 4. Plug the MV Power Plug Assy into one of the UPS receptacle provided on the back of the UPS 5. Dress the Mac Victor and UPS wiring cables with wire ties to secure any excess cabling 6.
5.4 Surge Monitor Operation This Mac Victor 2.0 standard feature monitors both the Input SPD Module and the Output Fuse (F1) on the Output Surge & Filter Board Assembly.
6 – MAINTENANCE / TROUBLESHOOTING 6.1 Input & Output Pilot Lights / UPS Bypass Switch This Mac Victor 2.0 standard feature is to provide a means to bypass the UPS for service and maintenance while still providing continuous and isolated power to all the connected equipment. Listed below are some troubleshooting tips based on the status of the input and output power pilot lights.
6.2 Input SPD Alarm / Output Fuse Indication Surge Monitor Operation: Standard Monitor and Alarm See Section 5.4 for complete operation and troubleshooting Figure 6.4 6.3 Circuit Breakers If any of the circuit breakers trip, a red indicator appears behind the clear plastic window on each breaker. To reset the breaker, switch to the “Off” position and then switch back to the “On” position. If a circuit breaker continues to open, check for a circuit overload or a wiring fault.
6.4 UPS (Uninterruptible Power Supply) See the UPS Installation / Operation Manual from the UPS manufacturer. 6.5 Troubleshooting Chart Problem Possible Cause Solution Connected loads not operating during normal operation Output circuit breakers turned off (See Section 6.3) Turn on the output breakers Connected loads not operating during loss of power UPS turned off Bypass switch in “bypass” mode (See Section 6.
6.6 Mac Victor 2.0 - Replacement Parts Mac Victor 2.0 Output SPD & Filter Board Assy. Fuse F-3 (Located at the bottom of the enclosure) Fuse F-2 Replacement Fuse F-1 Class CC - time delay / 8 amp THOR#: 0603-0004-01 Fuse F-1 (Output SPD fuse) Replacement Input SPD module THOR#: TSi040R-150-1P10 (Includes mounting base and replacement module) TB-1 Relay Output Power Figure 6.
7 – SPECIFICATIONS 7.1 Mac Victor 2.
Designed by: Mac Victor Power, LLC 6114 Prospect Street Fredericksburg, VA 22407 Phone: (540) 220-8116 Fax: (540) 242-7004 www.MacVictor.com Mac Victor® and Expand Your Power® are registered U.S. trademarks of Mac Victor Power, LLC Manufactured by: THOR SYSTEMS, INC. www.ThorSystems.US 804-355-1100 804-355-8900 fax 3621 Saunders Avenue Richmond, VA 23227-4354 Mac Victor 2.0 Installation Operation Manual 120711.pdf - © 2008 Mac Victor Power, LLC.