Brochure
Table Of Contents
Wireless Small Actuator -
 MAC-WSA
6 
Tunstall Corporation 
118 Exchange Street • Chicopee, MA 01013 
© July 2014 
We reserve the right to alter designs, specifications and information without notice. 
Phone (413) 594-8695 · Fax (413) 598-8109 
www.tunstall-inc.com • www.maconcontrols.com 
Bulletin-MC-WSA-1014 
Electric Operators 
EnOcean Equipment Profiles EEP 07-20-01 (heating valve) 
DATA BYTES  Notes 
Transmit mode:  Message from the actuator to the controller   
  DB_3:  Actual value 0 to 100%, linear n=0 to 100  ■ Positioning feedback of the current stroke position. 
 DB_2.BIT_7:   Service on  ■ BIT for evaluating whether service mode is active. 
When service mode is active, DB2.BIT4 to 7 can be 
used to carry out service functions like “Learn 
stroke” (not implemented in MAC-WSA); “Forced 
OPEN”; “Forced CLOSED”; and “Set zero point” – in 
combination with a suitable wireless partner. 
  DB_2.BIT_6:  Energy input enabled  ■ Not applicable for MAC-WSA 
        This BIT is required for actuators that have a wired 
power supply. 
  DB_2.BIT_5:  Energy memory > xx% charged  ■ Not applicable for MAC-WSA 
        This BIT is required for actuators that have a wired 
power supply. 
  DB_2.BIT_4:  Battery capacity > 10%  ■ Monitoring of the battery capacity If the capacity of the 
batteries is below 10%, a message of Bit4 = 0 is issued. 
 DB_2.BIT_3: Contact, cover open  ■ Not applicable for MAC-WSA 
        BIT for evaluation of a cover contact 
  DB_2.BIT_2:  Failure temperature sensor, out of range  ■ BIT for evaluation of whether the temperature sensor is 
working correctly. 
 DB_2.BIT_1: Detection, window open  ■ For evaluation of whether the “Window open” identifi-
cation is active. The “Window open” identification oc-
curs via the evaluation of the internal temperature sen-
sor (gradient). 
  DB_2.BIT_0:  Actuator obstructed  ■ Currently not used by MAC-WSA 
        All types of malfunctions are evaluated and reported 
(not in a differentiated manner, but only as a general 
malfunction message). 
  DB_1:  Temperature 0 °C to 40 °C / 32 °F to 104 °F,  ■ Current measurement value of the internal temperature 
       linear n=0 to 255    sensor 
 DB_0.BIT_7: Not used 
 DB_0.BIT_6: Not used 
 DB_0.BIT_5: Not used 
 DB_0.BIT_4: Not used 
  DB_0.BIT_3:  Learn button  0b0 Teach-in telegram  ■ The identification for the teach-in frame and the normal 
0b1 Data telegram    data frame is stored here. 
          The teach-in radiogram is only sent to the wireless 
          partner with the “Teach-in” function. 
 DB_0.BIT_2: Not used 
 DB_0.BIT_1: Not used 
 DB_0.BIT_0: Not used 