Non-Electric Operators
THERMOSTATIC OPERATOR
DIRECT MOUNT w/REMOTE SENSOR
MTWZ (Models T1-T4)
Operation
The sensor is wax-filled and the wax volume varies according to ambient temperature. The volume
changes are transmitted to the valve stem via a liquid capillary system. The valve body has a return
spring which closes the valve when the stem is under low pressure. When the force from the sensor and
the return spring are balanced to the room temperature selected, the valve disc stops in that position to
allow a certain amount of water or steam to flow through the valve. Temperature changes cause the
valve disc to change position and thereby continuously modulate the flow so that the room temperature
is maintained at the desired temperature. The unit is secured against damage from over pressure by a
pressure absorbing spring.
Features
 Valve-mounted setting knob and remote tem-
perature sensor
 Brass sensor, High sensitivity
 Fiberglass valve plug shaft
 Stainless steel capillary tube, 6’6” standard
length
 Longer capillary available, consult factory
 Fits all Macon NT series valves
 Replaces the valve-mounted sensors on built-
in convectors, etc., and where the valve-
mounted sensor is exposed to draft from
doors and windows
 Fully automatic - nonelectric, no wiring
 Manufactured to exacting standards using ex-
ceptionally high quality materials
 Each sensor is tested and re-checked to
achieve exact settings before leaving the fac-
tory
 Note that changing of the actuator can be ac-
complished without draining of the system
 All Macon thermostats can be locked at or
limited to a specific temperature or tempera-
ture range
 Simple one-trade installation
 Sensor guard furnished at no extra cost
 All Macon valves and thermostats conform to
ASHRAE Standard 102P-1983 and European
Standard EN 215/1215. We are also ISO 9001
certified (1994) and ISO 14001 certified
(1998).
See reverse for