Brochure
Table Of Contents
Tunstall Corporation 
118 Exchange Street • Chicopee, MA 01013 
© July 2014 
We reserve the right to alter designs, specifications and information without notice. 
Phone (413) 594-8695 · Fax (413) 598-8109 
www.tunstall-inc.com • www.maconcontrols.com 
Bulletin-MVA2-10V-0714 
Electric Operators 
Motorized Actuator 2-10 Volt 
MVA 2-10V
3 
Factory Setting: All the DIP switches in OFF position. 
DIP switches 1-2-3 
The DIP switches 1-2-3 are used for setting the control signal range. 
DIP switch 4 
The direction of operation of the actuator is set with DIP switch 4: 
DIP switch 4 in OFF position: DA (Direct Acting) 
DIP switch 4 in ON position: RA (Reverse Acting) 
DIP switch 5 
This switch can set the actuator so that the characteristic of the combination of 
valve with actuator corresponds to a linear or equal-percentage characteristic. 
DIP switch 5 in OFF position: LIN 
Use this setting if the valve has a linear or equal-percentage characteristic. 
DIP switch 5 in ON position: Eq% 
Use this setting with an open/close or a high-speed valve. 
DIP switch 6 
The voltage (VDC) or current (mA) is set with DIP switch 6. 
DIP switch 6 in OFF position: VDC 
DIP switch 6 in ON position: mA 
Setting the stroke 
The stroke can be set using a jumper. 
Factory Setting: 4.3mm 