Brochure

Tunstall Corporation
118 Exchange Street • Chicopee, MA 01013
© July 2014
We reserve the right to alter designs, specifications and information without notice.
Phone (413) 594-8695 · Fax (413) 598-8109
www.tunstall-inc.com • www.maconcontrols.com
Bulletin-ENTLZ-0714
Non-Electric Operators
THERMOSTATIC OPERATOR
w/REMOTE DIAL and REMOTE SENSOR
ENTLZ B56000
Operation
The sensor is wax-filled and the wax volume varies according to ambient temperature. The volume
changes are transmitted to the valve stem via a liquid capillary system. The valve body has a return
spring which closes the valve when the stem is under low pressure. When the force from the sensor and
the return spring are balanced to the room temperature selected, the valve disc stops in that position to
allow a certain amount of water or steam to flow through the valve. Temperature changes cause the
valve disc to change position and thereby continuously modulate the flow so that the room temperature
is maintained at the desired temperature. The unit is secured against damage from over pressure by a
pressure absorbing spring.
Features
Combined remote dial/sensor
Brass sensor, High sensitivity
Fiberglass valve plug shaft
Stainless steel capillary tube, 6’6” x 6’6” std.
length
Longer capillary available, consult factory
Fits all Macon NT series valves
Replaces the valve-mounted sensors on built-in
convectors, etc., and where the valve-mounted
sensor is exposed to draft from windows or
doors
Fully automatic - nonelectric, no wiring
Small dimensions
Manufactured to exacting standards using ex-
ceptionally high quality materials
Each sensor is tested and re-checked to achieve
exact settings before leaving the factory
Note that all changing of the actuator can be
accomplished without draining the system
All Macon thermostats can be locked at or lim-
ited to a specific temperature or temperature
range
Simple one-trade installation
Sensor guard furnished at no extra charge
All Macon valves and thermostats conform to
ASHRAE Standard 102P-1983 and European
Standard EN 215/1215. We are also ISO 9001
certified (1994) and ISO 14001 certified (1998).