Brochure

ELECTRIC ZONE VALVE ACTUATOR
ZMC - ES Series
Tunstall Corporation
118 Exchange Street • Chicopee, MA 01013
© July 2014
We reserve the right to alter designs, specifications and information without notice.
Phone (413) 594-8695 · Fax (413) 598-8109
www.tunstall-inc.com • www.maconcontrols.com
Bulletin-ZMC-ES-0714
Electric Operators
2
2.2 Function Display
The function indicator of the Macon ZMC - ES (all around view) allows identifying the operating condition (valve open or
closed) at a glance. It is also possible to feel the current operating state when it’s dark.
In case of the NC version, an extended function display
shows opening of the valve.
2.3 “First Open” function (for NC only)
In its delivery condition, the Macon ZMC - ES is kept open when de-energized due to the First-Open function. This enables
heating operation during the construction phase even when the electric wiring of the individual room control is not yet com-
plete. During the later electrical start-up, the First Open function is automatically unlocked by applying the operating voltage
for more than 6 minutes. The valve drive is now fully operable.
3) Technical Data
Operating voltage 24 V AC/DC +20%...-10%
Max. inrush current < 300 mA during max. 2 min.
Operating power 1 W
1)
Stroke (actuator travel) 4.0 / 5.0 mm
Actuating force 100 N ±5%
Switching current for micro switch 24 V AC: 3 A resistive load 1 A inductive load
Switching point of micro switch NC approx. 2 mm
Fluid temperature 32° F - 212° F
2)
Storage temperature -130° F - 140° F
Ambient temperature 32° F - 140° F
Degree / class of protection IP 54
3)
CE conformity according to EN 60730
Housing material / color Polyamide / light grey (RAL 7035)
Connection line / color 4 x 0.75 mm² PVC / light gray (RAL 7035)
Cable length 3’ 3”
2) depending on the adapter
even higher
Weight with connecting cable (1 m) approx. 5.3 oz
Surge protection according to EN 60730-1 min. 2.5 kV 3) in all installation positions
1) measured with precision
reference meter LMG95