Non-Electric Operators 
THERMOSTATIC OPERATOR 
DIRECT MOUNT w/REMOTE SENSOR 
MTWZ
Each unit is factory pre-set per dial settings listed. 
If field adjustments are necessary, see below. 
Maximum setting 
1.  Turn the wheel to maximum and a red mark will 
occur in the indicating window (located opposite 
the dial setting window). 
2.  Push the mark in while turning the wheel to de-
sired temperature according to below chart. 
3.  When reached desired temperature let go of the 
mark and the maximum temperature limit is set. 
Minimum setting 
1.  Turn the wheel to minimum and a blue mark will 
occur in the indicating window (located opposite 
the dial setting window). 
2.  Push the mark in while turning the wheel to de-
sired temperature according to below chart. 
3.  When reached desired temperature let go of the 
mark and the minimum temperature limit is set. 
DATA 
Temp. Range: 46° - 82°F 
Hysteresis: 0.9°F 
Heat Transfer: 1.1°F (Valve Housing Sensor) 
Dead Time: 0.8 Minutes 
Max. Differential Pressure: 20 psi 
Suggested Differential Pressure = 0.5 to 2.9 psi 
Max. Water Temp.: 250°F 
Max. Storage & Ambient Temp.: 122°F 
Max. Steam Pressure: 15 psig 
Max. Movement: 0.125 
Long Term Test: 5000 cycles (1.3°F) 
DIAL SETTINGS: 
* = 46°F (Frost Protection) 
1 = 54°F 
3 = 61°F 
5 = 68°F 
6 = 72°F 
7 = 76°F 
8 = 80°F 
9 = 82°F 
2.05 
3.66 
6’6” 
.93 
2.50 
SENSOR PROVIDED 
WITH GUARD 
(GUARD NOT SHOWN) 
ANGLE VALVE 
BODY 
THERMOSTATIC DIAL 
INSIDE ENCLOSURE 