Brochure
Table Of Contents
ELECTRIC ZONE VALVE ACTUATOR 
ZMC - DDC Series
Tunstall Corporation 
118 Exchange Street • Chicopee, MA 01013 
© July 2014 
We reserve the right to alter designs, specifications and information without notice. 
Phone (413) 594-8695 · Fax (413) 598-8109 
www.tunstall-inc.com • www.maconcontrols.com 
Bulletin-ZMC-DDC-0714 
Electric Operators 
2 
2.2 Function Display 
The function display (all-round display) of the Macon ZMC - DDC shows at first glance whether the valve is open or closed; 
this can be also felt in the dark. 
•  In case of the NC version, an extended function display 
shows opening of the valve. 
2.3 “First Open” function (for NC only) 
In its delivery condition, the Macon ZMC-DDC is normally open due to the “First Open” function. This enables heating op-
eration during the construction phase even when the electric wiring of the single room control is not yet complete. When 
commissioning the system at a later date, the "First Open" function is automatically unlocked by applying the operating volt-
age (for more than 6 minutes) and the actuator is fully operable. 
3) Technical Data 
Voltage (according to variant) 
24 V AC, -10% … +20-%, 50-60 Hz 
24 V AC, -20% … + 20%, 
Control voltage range  0 V … 10 V (reverse polarity protected)   
Max. inrush current  < 300 mA during max. 2 min.   
Operating power  1 W 
1)
Resistance of control voltage input 
100 kΩ 
Stroke (actuator travel)  4.0 / 5.0 mm (minus 0.5 mm over-elevation)   
Actuating force  100 N ± 5%   
Fluid temperature  32° F - 212° F 
2)
Storage temperature  -130° F - 149° F   
Ambient temperature  32° F - 140° F   
Degree / class of protection  IP 54 
3)
 / III   
CE conformity according to  EN 60730   
Housing material / color  Polyamide / white 
1) measured with precision 
reference meter LMG95 
Connection line / color  3 x 0.22 mm² PVC / white 
Cable length  3’ 3” 
2) depending on the adapter 
even higher 
Weight with connecting cable (1 m)  approx. 3.9 oz 
Surge protection according to EN 60730-1  min. 1 kV  3) in all installation positions 
If a 4 mm actuator without valve path recognition is used or 
valves with an actuator travel of 3 mm, the actuator ravels 
without load for control voltages from 7.5 V to 10 V. 










