Brochure
Table Of Contents
Tunstall Corporation 
118 Exchange Street • Chicopee, MA 01013 
© July 2014 
We reserve the right to alter designs, specifications and information without notice. 
Phone (413) 594-8695 · Fax (413) 598-8109 
www.tunstall-inc.com • www.maconcontrols.com 
Bulletin-OPSK-0714 
Non-Electric Operators 
ONE-PIPE STEAM VALVE ASSEMBLY
OPSK
OPERATION 
The Macon one-pipe steam valve assembly con-
sists of the reliable MTW direct mounting ther-
mostat. The thermostatic head contains a tem-
perature sensitive wax which expands and con-
tracts on a rise and fall of temperature in the 
sensed area. When the temperature rises above 
the temperature selected, pressure from the ex-
panding wax closes the valve, preventing or re-
stricting the flow of steam through the radiation 
unit. When the room temperature drops below the 
selected temperature, the valve opens and allows 
an increase of steam flow through the radiation 
unit. This modulating process continues automati-
cally to maintain the temperature you selected. 
The OPSK controls room temperature by regulat-
ing the amount of air and steam in the radiator. 
FEATURES & BENEFITS 
•  Compact dimensions 
•  Nickel-plated, forged brass valve 
•  Thermostat may be locked at or limited to any 
desired temperature or temperature range 
•  Actuators may be changed without shutting 
down the system 
•  Valve may be installed by dropping the sys-
tem down to zero pressure 
•  Individual room control for greater comfort 
•  Replaceable insert 
•  Stainless steel spindle 
•  Fuel savings up to 30% 
•  Nonelectric - fully automatic 
•  Prevents over- and under-heating 
•  Reliability 
•  Remote thermostats available - call or write 
for the distributor nearest you! 
•  Vent and vacuum breaker included 
•  The OPSK helps to minimize large tempera-
ture swings inherent in one pipe steam sys-
tems. 
OPTIONS 
The OPSK can be fitted with the following 
thermostatic operators: 
•  MTW (Standard) - direct mount 
•  MTWZ - direct mount w/remote sensor 
•  ENTL - remote dial 
•  ENTLZ - remote dial w/remote sensor 
•  VM Series - electric actuator 
•  Other operators available - contact factory 
Important: 
1.  Installing the OPSK does not eliminate other controls in the system. The boiler must be cycled in some manner so that 
condensate can return to the boiler and eliminate boiler flooding. 
2.  If the boiler is cycled from a space thermostat in one zone, do not apply a radiator valve to that zone’s radiation. 
3.  Do not apply a radiator valve in a one-pipe steam system that does not use steam air vents venting to the atmosphere on 
each radiation unit. 
4.  The VB-18 vacuum breaker is recommended and assists in the return of condensate. Integral installation reduces vacuum 
problems. 
5.  Very effective with system pressure range 0-1½ PSI. Suggested maximum operating pressure 2 PSI. 










