Warranty & Engineering Data 
SPECIFICATIONS 
Macon Controls
Valves - Macon Straight, Vertical Angle, Horizontal Angle or Copper x Copper Sweat as Required: 
Forged brass, nickel plated, female inlet, male union outlet or copper x copper brass body. 
EPDM seat suitable for 15 psi steam, 250°F hot water, maximum static pressure 145psi. 
Replaceable insert assembly with raised knurled serrations and stainless steel spindle and stainless steel spring. 
Vertical Angle Valve with straight 
nipple. NPT - female inlet, male 
union outlet. 
½” N10637 
¾” N10657 
1” N10677 
1¼” N10697 
Straight valve with straight nipple 
NPT - female inlet, male union 
outlet. 
½” N10737 
¾” N10757 
1” N10777 
1¼” N10797 
  Horizontal angle valve with 
straight nipple. NPT - female 
inlet, male union outlet. 
½” N10837 
¾” N10857 
1” N10877 
1¼” N10897 
  Sweat valve with female 
inlet and outlet. 
½” N10930 
¾” N10950 
1” N10970 
Direct Mount Thermostat - Macon Model MTW:
Direct acting, built in sensor, wax filled, hysteresis .9°F, max movement per 1°F = .007 
Range 46°-82°F with limit and locking features 
Must have positive shut off, maximum differential pressure 20psi H2O 
Heat diffusing rings and knurled serration that lock the thermostatic dial to the valve body 
Tamper proof, Non-Removable high impact plastic protection rings 
12 month warranty, and must conform to ASHRAE Standard 102p-1983 
MTW 
Remote Sensor Thermostat - Macon Model MTWZ:
Valve mounted setting knob with remote temperature sensor 
Capillary to be stainless steel, 78” long minimum 
Provide high impact plastic sensor guard 
Temperature range 46-82°F, with limit and locking features 
Must have positive shut off, maximum differential pressure 20psi H2O 
Heat diffusing rings and knurled serration that lock the thermostatic dial to the valve body 
12 month warranty, and must conform to ASHRAE Standard 102p-1983 
MTWZ 
(Shown with Valve) 
Remote Dial Thermostat Model Macon ENTL-B46000: 
Remote mounted dial with sensor behind dial, minimum 78" stainless steel capillary 
High impact plastic dial operator, range 46°-80°F with limit and locking features 
Must have positive shut off, maximum pressure differential 20psi H2O 
12 month warranty, and must conform to ASHRAE Standard 102p-1983 
ENTL B46000 
(Shown with Valve) 
Combination Remote Dial / Remote Sensor Thermostat - Macon Model ENTLZ-B56000:
Combination remote setting dial/remote sensor, minimum 78" stainless steel capillary to 
Setting dial and 78" stainless steel capillary to temperature sensor 
Requires the capability to remove temperature sensor from dial with minimum 78" S.S. capillary 
Provide high impact plastic sensor guard 
Temperature range 46-80°F, with limit and locking features 
Must have positive shut off, maximum differential pressure 20psi H2O 
12 month warranty, and must conform to ASHRAE Standard 102p-1983  ENTLZ B56000 