Technical data

124
OR
PLE-104
Pooja Lab, India
Model No. IF-050
System- In GMP bin is SS- 316 and exterior is SS-304 mat finish. Built-in well-insulated bin keeps the ice for longer period. A
metallic/non-metallic door provided at the top of the bin for easy removal of ice. Automatic cut-off takes place when the bin is full
and starts again as soon as level comes down. Guaranteed Ice production @ 20
0
C air and 15
0
C DM water temperature
Additional Safety System – The Ice Flaker is supplied with water filter and water failure protection device by considering that the
unit will not RUN in case of water supply fails and it starts automatically when the water supply resumes at an extra cost.
Pre-Installation Requirement – Stabilized 230V 50HZ AC single-phase 15 amps power supply with MCB and proper earthing within
the radius of one meter from the installation. One feet free space around for installation in an air-conditioned or in a cross ventilated,
dust free and clean environment. (Room temperature should be below 30 deg. C) Zero level flooring and floor level drainage within
the radius of one meter from the installation. Continuous DM or Distilled water supply line ½” BSP with nipple valve connection
within the radius of one meter from the installation.
Capacity- 50kg./ 24 hours , Bin Capacity- 20kg. approx
External Dime inch/mm exclusive of water filter assembly
W x D x H - 24.00 x 24.00 x 38.98 (610 x 610 x 990)
OR
Model No. IF-030
System- In GMP bin is SS- 316 and exterior is SS-304 mat finish. Built-in well-insulated bin keeps the ice for longer period. A
metallic/non-metallic door provided at the top of the bin for easy removal of ice. Automatic cut-off takes place when the bin is full
and starts again as soon as level comes down. Guaranteed Ice production @ 20
0
C air and 15
0
C DM water temperature
Additional Safety System – The Ice Flaker is supplied with water filter and water failure protection device by considering that the
unit will not RUN in case of water supply fails and it starts automatically when the water supply resumes at an extra cost.
Pre-Installation Requirement – Stabilized 230V 50HZ AC single-phase 15 amps power supply with MCB and proper earthing within
the radius of one meter from the installation. One feet free space around for installation in an air-conditioned or in a cross ventilated,
dust free and clean environment. (Room temperature should be below 30 deg. C) Zero level flooring and floor level drainage within
the radius of one meter from the installation. Continuous DM or Distilled water supply line ½” BSP with nipple valve connection
within the radius of one meter from the installation.
Capacity- 30kg./ 24 hours
Bin Capacity- 20kg. approx
External Dime inch/mm exclusive of water filter assembly
W x D x H - 24.00 x 24.00 x 38.98 (610 x 610 x 990)