CM-E1 Carbon Monoxide Detector

Other 3M
Macurco
Carbon Monoxide Detector
CM-E1 Features
3M and Macurco are trademarks of 3M.
Tygon is a registered trademark of
Saint-Gobain Corporation.
NFPA is a trademark of National Fire
Protection Association.
Please recycle. Printed in USA.
© 2009 3M Company. All rights reserved.
70-0714-8856-6
Occupational Health &
Environmental Safety Division
3M Center, Building 235-02-W-70
St. Paul, MN 55144-1000
www.3M.com/OccSafety
For More Information
In U.S., contact:
Website: www.3M.com/Macurco
Technical Assistance: 1-800-243-4630
UL Standards:
Listed to UL Standard 2075, Standard for Safety for
Gas and Vapor Detectors and Sensors.
Tested to UL 2075 using UL 2034 sensitivity limits for
carbon monoxide gas.
Flush or Surface Mountable:
Surface mounts to a
wall using the supplied
enclosure rear housing.
Flush mounts in a 2" x 4"
(1½" deep minimum)
single gang switch or
handy electrical box.
Testing:
Test & Reset switch conducts internal tests and
actuates Alarm Relay.
N.O. or N.C. SPST Alarm Relay and N.C. SPST
Trouble Relay to connect to Alarm Control Panels.
Produces repeating loud tone bursts or buzzes
during alarm and chirps if sensor trouble is found.
Microcomputer control allows for a mostly
automatic operation.
Visual Display:
GREEN: Normal operation.
FLASHING AMBER: Trouble, contact your
installer or 3M Macurco Tech Support.
RED: Danger! Move to fresh air
(hazardous condition is present).
Specifications:
Voltage: 9-32 VDC
Current (normal/alarm):
15mA /35mA @ 9-32V
Size: 3
1
8" x 5
1
8" x 1½"
Alarm Relay: SPST, 100mA, 40VDC
Trouble Relay: SPST, 100mA, 40VDC
Buzzer Rating: 85 dBA at 10 feet
Shipping Weight: One pound
Operating Temp. Range: 40° to 100° F
Alarm Setting: Per UL 2034
Color: White
Designed for use with
a UL Listed alarm
control panel. (May be
used with a UL Listed
Class 2 Power Supply.)
WARNING
IMPORTANT: To help avoid false alarms, the CM-E1 is not intended for low level
detection (below 30ppm) of Carbon Monoxide, per UL 2034. Individuals with
medical problems should consider using warning devices that provide audible and
visual
signals for carbon monoxide concentrations under 30ppm.
The CM-E1 is intended for use in ordinary indoor locations of family living
units and
office work spaces. It is not designed to measure compliance with
Occupational
Safety and Health Administration (OSHA) commercial or
industrial standards.
Part No. Description Stock No. UPC No.
Qty/Case
CM-E1 3M
Macurco
Carbon Monoxide Detector 70-0715-4473-1 0 00 51131 17287 6 10
CM-E1-FTG-CA
3M
Carbon Monoxide Field Test Gas 11L 500 PPM CO/Air,
Aerosol (for use with CM-E1 CO functionality test)
70-0715-4465-7 0 00 51131 17274 6 12
CM-E1-FTK
3M
Carbon Monoxide Field Verification Gas Kit includes 17L 200
PPM CO/Air, regulator, test hood and Tygon
®
tubing (for use with
CM-E1 CO sensitivity test)
70-0715-3441-9 0 00 51131 17238 8 1
Alarm Relay: SPST
100mA, 40VDC dry
contacts, no polarity
Trouble Relay: SPST
100mA, 40VDC dry
contacts, no polarity
Power Source:
9 to 32VDC
Note: There is a jumper on the PCA to change the alarm output.
Remove the jumper for N.C. or leave the jumper in place for N.O.
CM-E1
Alarm
Relay
Blue
Yellow
Green
Gray
Black (-)
Red (+)
Trouble
Relay
GND
9-32VDC
CM-E1
GND
N.O. Initiating
circuit
Battery-backed 12 or 24
VDC Power Supply. Fuse
or current limit at 0.2 A for
each CM-E1
UL Listed Alarm Control Panel
Typical connection of two CM-E1 detectors to an alarm control panel:
Alarm
Relay
Yellow
Blue
Green
Gray
Black (-)
Red (+)
Trouble
Relay
N.C.
GND
9-32VDC
CM-E1
E.O.L.R.
Alarm
Relay
Yellow
Blue
Green
Gray
Black (-)
Red (+)
Trouble
Relay
N.C.
GND
9-32VDC