Macurco™ DVP-120 Detection and Ventilation Control Panel User Instructions IMPORTANT: Keep these User Instructions for reference.
TABLE OF CONTENTS 1 1.1 1.2 1.3 1.4 1.5 Introduction General Information Features Specifications Warranty Return Instructions 4 4 4 5 5 5 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Installation & Connection Mounting the DVP-120 General Wiring Information Main power Connection Remote Sensor Connection Relay Connection Horn & Strobe Connection Interfacing Macurco Sensors 5 6 6 7 8 9 9 10 2 3 Operation 3.1 Initial Operating Mode 3.1.1 Status Light Display 3.1.2 User Interface 3.1.3 Normal Status Display 3.1.
.3.6.4 Strobe Minimum On Time 3.3.7 Configure Zones Submenu 3.3.7.1 Zone Controls 3.3.7.2 Zone Group Type 3.3.7.3 Timed Day Selection 3.3.7.4 Start Time 3.3.7.5 Stop Time 3.3.7.6 Sensor Selection 3.3.7.7 Rising Trip Point 3.3.7.8 Falling Trip Point 3.3.7.9 Multiple Sensor Mode 3.3.7.10 Multiple Sensor Quorum 3.3.8 Configure Signals Submenu 3.3.8.1 Alarm Signal Summary 3.3.8.2 Alarm Buzzer Signal 3.3.8.3 Alarm Horn Signal 3.3.8.4 Alarm Strobe Signal 3.3.8.5 Warning Signal Summary 3.3.8.
LIST OF WARNINGS ! WARNING Each person using this equipment must read and understand the information in these User Instructions before use. Use of this equipment by untrained or unqualified persons, or use that is not in accordance with these User Instructions, may adversely affect product performance and result in sickness or death. Use only for monitoring the gases which the sensors and equipment are designed to monitor.
Operating Temperature: Operating Humidity: Power Input: Relay Rating (3): LCD Display: Status Indicators (LED): Audible indicator: External Drivers (2): Carbon Monoxide (CO) Range: Nitrogen Dioxide (NO2)Range: Combustible (EX) Range: Ammonia (NH3) Range: Hydrogen Sulfide (H2S) Range: Refrigerant (REF) Range: Oxygen (O2) Range: Carbon Dioxide (CO2) Range: Wild Card (WC) Range: Relay On Delay: Relay Minimum Run Time: 32 to 104°F (0° to 40°C ) 0% to 95% RH non-condensing
This system should be used with Macurco™ transducers and each unit will measure the level of the target gas (i.e. CO, NO2, EX) and provide this information to the DVP-120 over a 4-20mA current loop. The transducers operate on low voltage (24VDC). All power and signal connections for the transducers are provided from the DVP-120 control panel, via unshielded four conductor cable. Be sure that the 4-20mA output on each sensor is set to “On”.
2.2 General Wiring Information ! WARNING High voltage terminals (120/240 VAC) are located within the DVP-120, presenting a hazard to service technicians. Only qualified technicians should open the DVP-120 case and service the internal circuits. Ensure power is removed from the DVP-120 prior to servicing the unit. With the exception of the safety ground, all field wiring is completed via modular connectors (provided).
Signal Line (120/220/240/250 VAC) Neutral Ground Connector AC~ AC~ Ground Stud Pin Number 3 1 n/a Table 2-1 Main Power Connections Figure 2-4 DVP-120 Internal View 2.4 Remote Sensor Connection Each remote sensor is connected by a four-wire connection – two wires for DC power and two wires for the 4 – 20 mA loop connection. Be sure that the 4-20mA output on each sensor is set to “On”. The sensors are connected to the control panel PCB with modular connectors, two sensors per connector.
Figure 2-5 Sensor Interface Connector – Channels 5 and 6 Each 8-terminal sensor modular connector may be disconnected from the PCB connector to ease wire installation. The terminals will accept wire from 16 to 28 AWG. To install a wire, strip back approximately 0.25 in. (6 mm) of insulation, and insert the bare wire into the terminal. Tighten the screw clamp and ensure that the wire cannot be easily pulled from the connector. Connector to sensor C1 through C12 correspondence to all 12 input channels.
To install the wiring for the relays, disconnect the connector from the header on the PCB. Strip the insulation of each wire back approximately 1/4 in. (6.5 mm), insert the bare wire into the terminal and tighten the screw clamp. Ensure that the wire cannot easily be pulled from the connector. 2.6 Horn & Strobe Connection The external horn and strobe connections are available at the modular connector S H (see Figure 2- for details). S H as a 4-position connector, similar to the sensor interface connectors.
3 Operation 3.1 Initial Operating Mode When power is first applied to the DVP-120, a few simple self-tests will be performed, and the system will cycle through all status lights, and display the system name and model # (Figure 3-1). The system will then proceed to normal mode, if the operating parameters have been entered. DV P - 1 2 0 V e r 1 . 0 7 Figure 3-1 Model Display ! WARNING Each time the unit is turned on it performs a self-test, which activates the audible and visual alarms.
RELAY 2 Off – Relay 2 is not on Green (steady) – Relay 2 is on RELAY 3 Off – Relay 3 is not on Green (steady) – Relay 3 is on The overall system status is visible at a distance via the status lights as described above. More detailed system information is displayed on the LCD, which can show the status of each relay and sensor. A typical status display is shown in Figure . 3.1.
3.1.3 Normal Status Display MON S0 1 1 0 : 2 3 CO R1 5 OFF PPM Figure 3-4 Normal System Display The display shows the day of the week and the time of day, in 24-hour format. It also shows the status of one of the relays, R1 in this example, and the type and indicated gas concentration of one of the configured sensors, S01 is a CO sensor indicating 5 ppm in this example.
When all indicators have been silenced, the display will show that alarms have been silenced for five minutes. After any key is pressed (or five seconds), the display will return to normal mode. A L ARM FOR 5 S I LENCED M I NUTES Figure 3-7 Alarm Silenced message If Relay 1 is configured as an ALARM relay, it will be turned on when an alarm condition is recognized and will be turned off when all audio indicators have been silenced using the HUSH key. 3.1.
The display will cycle through all trouble indications, at five seconds per display. Pressing any key (except HUSH) will advance the display to the next trouble indicator. If an external horn and/or strobe are connected and configured to signal a trouble condition, they will also sound when a trouble condition occurs, after a delay, if that configuration option is selected. When the HUSH key is pressed, the internal buzzer will be silenced for eight (8) hours.
entry in the top menu summarizes the number of sensors and relays that the panel is currently recognizing. Be sure that the 4-20mA output on each sensor is set to “On”. 5 3 SENSORS FOUND RE L AYS FOUND Figure 3-14 Hardware Summary The MENU key is also used to return to a higher-level menu and finally exit the configuration menus back to normal mode. When exiting from the menu system to normal mode, if any configuration changes have been made, the panel will ask whether changes are to be saved.
3.3.1 Configure System Submenu The system configuration submenu provides entries to: – Set the time of day, 24 hour format – Set the day of the week, day 1 is Monday – Load Default Configuration – Change Password – Configure Sensor Type 3.3.1.1 Set Time of Day T i me : 2 2 : 5 5 Da y : T u e s d a y Figure 3-16 Set Time of Day This display example shows that the time is 22:55 (10:55 PM). The underlined characters indicate that the numeric keys can be used to set the current time of day.
3.3.1.3 Load Default Configuration 1 L o a d De f a u l t Co n f i g u r a t i o n Figure 3-20 Load Default Configuration When the number one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously. If the password is entered correctly, the panel will overwrite the existing configuration with the default configuration. This operation is intended to restore the panel to a known basic condition if it is removed from one installation and installed in another.
3.3.1.5 Configure Sensor Type Sensor Registration Sensor registration is continuously monitored by the DVP-120. When the currently selected sensor type agrees with the stored registration information the DVP-120 will remain in normal mode. When new registration information is detected by the DVP-120, for example if a different gas type of Macurco sensor was installed, the following message is displayed: “Configuration Changed Any key to save” is displayed. Config. changed Any key to save Figure 3-21.
Type:01 CO Depletion: 0 No Figure 3-21.6 Depletion Type “Depletion” is “1” when the sensor is a depletion type and “0” when it is not a depletion type sensor. A depletion sensor detects when gas concentrations in a space fall below a specified level. Type:01 CO Dec.:0 8888. ppm Figure 3-21.7 Decimal Points “Dec.” defines how many decimal points are used to display the reading, alarm, warning, range, rising and falling levels. It can have values between 0 and 2. Type:01 Res.: CO 1 ppm Figure 3-21.
Type:01 CO Fall: 15 ppm Figure 3-21.13 Falling Trip Point “Fall” is the default falling level used in Zone configuration. For the custom sensor types default parameters are set to display the current measured above 4 mA. So if the current is 4 mA, it displays 0.00 mA. And when the current is 20 mA it displays 16.00 mA. 3.3.1.6 Enter Password If the password has not yet been entered, when the first digit of any parameter is entered, the panel will prompt for the current password.
This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide sensor with an Alarm level of 200 ppm and a Warning level of 50 ppm. Notice that the sensor number, 01 in this example, is underlined. This indicates that the digit keys can be used to jump to a particular channel, even if there is no sensor connected to the channel. 3.3.2.
3.3.2.5 Range Se n s o r Ra n g e : 0 1 CO 2 0 0 p pm Figure 3-29 Sensor Range The range for each sensor is the gas concentration that corresponds to the 20 mA signal level. The default range values for the sensors are: Description Carbon Monoxide Nitrogen Dioxide Combustible Gas Ammonia Hydrogen Sulfide Refrigerants Carbon Dioxide Oxygen Range 200 ppm 20 ppm 50% 100 ppm 50ppm 1,000 ppm 5,000ppm 25% 3.3.
The default turn on delay is one minute and the maximum allowed value is fifteen minutes. The value is entered in two groups, 2 digits for the minutes and then 2 digits for the seconds. A leading zero must be entered for each group if applicable. 3.3.3.4 Relay Minimum On Time Re l a y 1 ( mm : s s ) M i n . On 0 1 : 0 0 Figure 3-33 Minimum on time The default minimum on time is one minute and the maximum allowed value is fifteen minutes. 3.3.
3.3.5 Configure Strobe Submenu The configuration parameters for the strobe are the same as those for relays. A strobe would not normally require a minimum on time but this parameter allows a more versatile configuration. 3.3.5.1 Strobe Summary S t r o b e 5 No r m . O f f De l a y On Figure 3-38 Strobe Summary This display example shows that the strobe has been configured to operate Normally Off, with a turn on delay and no minimum on time. Notice that the strobe number, 5, is underlined.
The default Ventilation Controls are: Zone 1 controls Relay 1 Zone 2 controls Relay 2 Zone 3 controls Relay 3 3.3.6.1 Zone Controls Z o n e 1 C on t r o l s R1 R2 R3 H4 S5 Figure 3-42 Zone Controls This display example shows that Zone 1 is configured to control all of the relays plus the horn and the strobe. Each of the relays, the horn and the strobe can be removed from (or added to) the zones control by pressing the indicated digit key.
Group 3 in each zone Group 4 in each zone Group 5 in each zone Group 6 in each zone Group 7 in each zone Group 8 in each zone Type 3 EX, Voting mode, Quorum = 1 Type 4 NH3, Voting mode, Quorum = 1 Type 5 H2S, Voting mode, Quorum = 1 Type 6 REF, Voting mode, Quorum = 1 Type 7 CO2, Voting mode, Quorum = 1 Type 8 O2, Voting mode, Quorum = 1 Timed mode turns the zone’s outputs on at the START TIME if the current day is a weekday (or a weekend) and turns them off at the next occurrence of STOP TIME.
When the second digit is entered, the sensor will be added or removed from the control group, provided the sensor is of the proper type, NO2 in this example. If the sensor is of the wrong type, or an invalid sensor channel number is entered, the request will not be completed. 3.3.6.7 Rising Trip Point Z 1 Gr o u p R i s in g : 1 NO2 2 .
3.3.6.10 Multiple Sensor Quorum Z 1 G r o u p 1 Qu o r um : _ 2 NO2 Figure 3-52 Quorum Entry It is up to the installer to ensure that the quorum entry is appropriate for the configuration. Valid entries are one to twelve, but a value greater than the number of sensors being monitored by the group, stops the group from controlling the outputs. The default quorum value is 1. 3.3.
3.3.7.4 Alarm Strobe Signal A l a r m S i g n a l s S t r o b e : 1 Co n t i n . Figure 3-56 Strobe Alarm Signal This display example shows that the strobe will signal an alarm condition with a continuous signal. The signal definitions are: – 1 Continuous (default) – 2 Intermittent, one second on at two second intervals – 3 Double tap, two beeps at 5 second intervals – 4 Triple tap, three short beeps at 15 second intervals – 5 Off, strobe will not flash 3.3.7.
This display example shows that the strobe will not signal a warning condition. The signal definitions are: – 1 Continuous – 2 Intermittent, one second on at two second intervals – 3 Double tap, two beeps at 5 second intervals – 4 Triple tap, three short beeps at 15 second intervals – 5 Off, strobe will not flash (default) 3.3.7.9 Trouble Signal Summary The trouble signals are in response to one or more sensor faults, either as a defined current level, or because of wiring problems.
4 Troubleshooting The DVP-120 is tested at the factory for reliable operation. Most problems can be traced to the set-up of configurable features and modes, system wiring or trouble with the sensors. ! WARNING Do not disassemble unit or attempt to repair or modify any component of this instrument. This instrument contains no user serviceable parts, and substitution of components may adversely affect product performance and result in sickness or death. 4.
4.1.1.5 Resettable Fuse Each sensor channel is provided with a PTC-resettable fuse internal to the DVP-120 to protect against over current situations. To reset a sensor channel, power should be removed from the channel. This can be accomplished by removing power from the sensor – causing the loop current to go to zero, or by completely removing power from the DVP-120. 4.1.
Appendix A – Quick Set-up IMPORTANT: To properly and effectively program the system you must configure the Sensors, Relays, Zones and Signals. If the user has not entered any parameters, the system WILL NOT be monitoring the sensors or controlling the ventilation system. The relays will be in the not actuated state and the horn and strobe outputs will be off. Be sure that the 4-20mA output on each sensor is set to “On”. 1.
Group 2 in each zone Group 3 in each zone Group 4 in each zone Group 5 in each zone Group 6 in each zone Group 7 in each zone Group 8 in each zone Type 2 NO2, Voting mode, Quorum = 1 Type 3 EX, Voting mode, Quorum = 1 Type 4 NH3, Voting mode, Quorum = 1 Type 5 H2S, Voting mode, Quorum = 1 Type 6 REF, Voting mode, Quorum = 1 Type 7 CO2, Voting mode, Quorum = 1 Type 8 O2, Voting mode, Quorum = 1 Description Carbon Monoxide Nitrogen Dioxide Combustible Gas Ammonia Hydrogen Sulfide Refrig
Setting the System Configuration The configuration menus can be entered from normal mode by pressing the MENU key. While in configuration mode, the user can review all configuration parameters to check the current operating conditions. 5 3 SENSORS FOUND RE L AYS FOUND Figure A-2 Hardware Summary The MENU key is also used to return to a higher-level menu, exit the configuration menus and finally return to normal mode.
T i me : 2 2 : 5 5 Da y : T u e s d a y Figure A-5 Set Time of Day This display example shows that the time is 22:55 (10:55 PM). The underlined numerals indicate that the numeric keys can be used to set the current time of day. When the first numeral is entered (and after the password is entered if required), the display will change to show that the hour portion of the time is currently being entered. Note that the time is saved as soon as the fourth numeral is entered.
When the first digit is entered, the panel will appear as follows: En t e r Pa s swo r d _ _ _ * Figure A-10 Password Prompt If the password is not entered correctly the panel will display as follows: Wr o n g Pa s swo r d Figure A-11 Wrong Password Prompt Once the current password has been entered, the panel will prompt for the configuration parameter being changed. If the password has been lost: 1. Power down the DVP-120 2.
Warning Level - set level if needed Se n s o r 0 1 Wa r n i nG : CO _ 5 0 p pm Figure A-15 Sensor Warning Level Sensor Range - default range is in system Se n s o r Ra n g e : 0 1 CO 2 0 0 p pm Figure A-16 Sensor Range Next Sensor - complete for all sensor channels 3. Configure Relays, Horn & Strobe Submenu 4.12 See section 3.3.4 Configure Relays, Horn & Strobe Submenu for more detail Press Menu to display Hardware Summary x 3 Configure Relays Relay 1 Re l a y De l a y 1 No r m .
4. Configure Zones Submenu 4.13 See section 3.3.7 Configure Zones Submenu for more detail Definitions: Zone – Defines Sensor Input & Relay / Alarm Output Group – Set of Sensors of same type and output within the same zone. Average – Activation based upon an average of sensors in a group Voting – Number of sensors needed to be above trip point to activate output Quorum – Number of sensors need to vote, 1 = any sensor.
Falling (off) Trip point Z 1 G r o u p F a l l i n g : 1 NO2 1 . 0 p pm Figure A-25 Falling Trip Point Entry The default falling trip points are: Description Carbon Monoxide Nitrogen Dioxide Combustible Gas Ammonia Hydrogen Sulfide Refrigerants Carbon Dioxide Oxygen Type Falling Level CO 15ppm NO2 1.2ppm EX 5% NH3 10ppm H2S 3ppm REF 50ppm CO2 800ppm O2 20.
A l a r m S i g n a l s Bu z z , Ho r n , S t r o b e Figure A-27 Alarm Signals Alarm Signal Buzzer (default 2 – Intermittent) Alarm Signal Horn (default 2 – Intermittent) Alarm Signal Strobe (default 1 – Continuous) A l a r m S i g n a l s Bu z z : 2 I n t e r m i t .