Installation Manual
18
3.3.1.3 Load Default Configuration
1 L o a
d
D
e
f
a
u
l
t
C
o n
f
i
g
u
r
a
t
i
o
n
Figure 3-20 Load Default Configuration
When the number one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously. If the
password is entered correctly, the panel will overwrite the existing configuration with the default configuration. This operation is
intended to restore the panel to a known basic condition if it is removed from one installation and installed in another.
The default configuration is:
Password 1234
Sensors Undefined
Alarm signals Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous
Warning signals Buzzer = Off, Horn = Off, Strobe = Off
Trouble signals Buzzer = Triple Tap, Horn = Off, Strobe = Off
Relay 1 Normally off, 1 minute turn on delay, 1 minute minimum on time
Relay 2 Normally off, 1 minute turn on delay, 1 minute minimum on time
Relay 3 Normally off, 1 minute turn on delay, 1 minute minimum on time
Horn Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Strobe Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Zone1 Controls R1,
Zone2 Controls R2,
Zone3 Controls R3
Group 1 in each zone Type 1 CO, Voting mode, Quorum = 1
Group 2 in each zone Type 2 NO2, Voting mode, Quorum = 1
Group 3 in each zone Type 3 EX, Voting mode, Quorum = 1
Group 4 in each zone Type 4 NH3, Voting mode, Quorum = 1
Group 5 in each zone Type 5 H2S, Voting mode, Quorum = 1
Group 6 in each zone Type 6 REF, Voting mode, Quorum = 1
Group 7 in each zone Type 7 CO2, Voting mode, Quorum = 1
Group 8 in each zone Type 8 O2, Voting mode, Quorum = 1
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type CO NO2 EX NH3 H2S REF CO2 O2
Range 200 ppm 20 ppm 50% 100 ppm 50ppm 1000 ppm 5,000ppm 25%
Alarm Level 200ppm 5ppm 20% 75ppm 20ppm 300ppm 3,000ppm 19.5%
Warning Level 100ppm 3ppm 15% 50ppm 14ppm 200ppm 2,000ppm 20.0%
Rising Level 35ppm 2.5ppm 10% 25ppm 8ppm 100ppm 1,000ppm 20.3%
Falling Level 15ppm 1.2ppm 5% 10ppm 3ppm 50ppm 800ppm 20.6%
3.3.1.4 Change Password
C
h a n g
e
P
a
s
s
w
o
r
d
*
*
*
*
Figure 3-21 Change Password
When the first digit is entered to change the password the panel will prompt for the existing password to be entered (if it hasn’t already
been entered), see section 3.3.1.5 for more detail. Once the current password has been entered, the panel will prompt for the new
password.