Installation Manual

20
Figure 3-21.6 Depletion Type
“Depletion” is “1” when the sensor is a depletion type and “0” when it is not a depletion type sensor. A depletion sensor detects when
gas concentrations in a space fall below a specified level.
Figure 3-21.7 Decimal Points
“Dec.” defines how many decimal points are used to display the reading, alarm, warning, range, rising and falling levels. It can have
values between 0 and 2.
Figure 3-21.8 Resolution
“Res.” Defines the resolution used to display the reading, alarm, warning, range, falling level and rising level. It can have values
between: 1 and 500 when “Dec.” is 0, 50.0 when “Dec.” is 1 and 5.00 when “Dec.” is 2.
Figure 3-21.9 Sensor Range
“Range” is the value displayed when current measured is 20mA.
Figure 3-21.10 Alarm Level
“Alarm” is the default alarm range.
Figure 3-21.11 Warning Level
“Warn” is the default warning range.
Figure 3-21.12 Rising Trip Point
“Rise” is the default rising level used in Zone configuration.
Type:01 CO
Rise: 35 ppm
Type:01 CO
Warn: 100 ppm
Type:01 CO
Alarm: 200 ppm
Type:01 CO
Range: 200 ppm
Type:01 CO
Res.: 1 ppm
Type:01 CO
Dec.:0 8888. ppm
Type:01 CO
Depletion: 0 No