Installation Manual

30
3.3.7.4 Alarm Strobe Signal
A l a r m
S
i
g
n
a
l
s
S t r o b
e
:
1
C
o
n
t
i
n
.
Figure 3-56 Strobe Alarm Signal
This display example shows that the strobe will signal an alarm condition with a continuous signal. The signal definitions are:
1 Continuous (default)
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, strobe will not flash
3.3.7.5 Warning Signal Summary
The warning signals are in response to one or more sensors indicating gas levels at or above the sensors’ configured warning level.
W
a r n i
n
g
S
i
g
n
a
l
s
B u z z
Figure 3-57 Warning Signals
This display example shows that warnings are signaled by the internal Buzzer only.
3.3.7.6 Warning Buzzer Signal
W
a r n i
n
g
S
i
g
n
a
l
s
B u z z :
5
O
F
F
Figure 3-58 Buzzer Warning Signal
This display example shows that the buzzer will not signal a warning condition. The signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, buzzer will not sound (default)
3.3.7.7 Warning Horn Signal
W
a r n i
n
g
S
i
g
n
a
l
s
H
o r n :
5
O
F
F
Figure 3-59 Horn Warning Signal
This display example shows that the horn will not signal a warning condition. The signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, horn will not sound (default)
3.3.7.8 Warning Strobe Signal
W
a r n i
n
g
S
i
g
n
a
l
s
S t r o b
e
:
5
O
F
F
Figure 3-60 Strobe Warning Signal