This display example shows that the strobe will not signal a warning condition. The signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, strobe will not flash (default)
3.3.7.9 Trouble Signal Summary
The trouble signals are in response to one or more sensor faults, either as a defined current level, or because of wiring problems.
T r o u b
l
e
S
i
g
n
a
l
s
B u z z
Figure 3-61 Trouble Signals
This display example shows that troubles are signaled by the internal buzzer only.
3.3.7.10 Trouble Buzzer Signal
T r o u b
l
e
S
i
g
n
a
l
s
B u z z :
4
T
r
i
p
l
e
Figure 3-62 Buzzer Trouble Signal
This display example shows that the buzzer will signal a trouble condition with a triple tap signal. The buzzer signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals (default)
5 Off, buzzer will not sound
3.3.7.11 Trouble Horn Signal
T r o u b
l
e
S
i
g
n
a
l
s
H
o r n :
5
O
F
F
Figure 3-63 Horn Trouble Signal
This display example shows that the horn will not signal a trouble condition. The horn signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, horn will not sound (default)
3.3.7.12 Trouble Strobe Signal
T r o u b
l
e
S
i
g
n
a
l
s
S t r o b
e
:
5
O
F
F
Figure 3-64 Strobe Trouble Signal
This display example shows that the strobe will not signal a trouble condition. The strobe signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, strobe will not flash (default)