Installation Manual
40
4. Configure Zones Submenu
4.13 See section 3.3.7 Configure Zones Submenu for more detail
Definitions:
Zone – Defines Sensor Input & Relay / Alarm Output
Group – Set of Sensors of same type and output within the same zone.
Average – Activation based upon an average of sensors in a group
Voting – Number of sensors needed to be above trip point to activate output
Quorum – Number of sensors need to vote, 1 = any sensor.
Press Menu to display Hardware Summary
x 4 Configure Zones
Zone 1 Controls
R_ R_ R_ H_ S_
Enter (underlined) number of output for zone
R = Relay (1, 2 and 3), H = Horn (4), S = Strobe (5)
Z o n e
1
C
o
n
t
r
o
l
s
R
1 R
2
R
3
H
4
S
5
Figure A-21 Zone Controls
Configure Group 1
Sensor type - enter #
1=CO, 2=NO2, 3=Combustible, 0=None
Z 1 G
r
o
u
p
1
N
O
2
S e n s o
r
T
y
p
e
:
2
Figure A-22 Zone Group Type
Sensor Number - enter a two digit number for each sensor to be included in the group (e.g., 01, 02, 03…12.) from 01 through 12.
Z 1 G
r
o
u
p
1
N
O
2
S e n s o
r
s
:
0
2
,
0
4
,
1
1
Figure A-23 Sensor Selection
Rising (activation) Trip point
Z 1 G
r
o
u
p
1
N
O
2
R
i s i n
g
:
2
.
5
p
p
m
Figure A-24 Rising Trip Point Entry
The default rising trip points are:
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type CO NO2 EX NH3 H2S REF CO2 O2
Rising Level 35ppm 2.5ppm 10% 25ppm 8ppm 100ppm 1000ppm 20.3%